Cable joints and terminations
Eaton PMIC2-403x70HS
Inner-cone GIS cable termination, size 2, 3-core, 26/35 kV, 70 mm²
Dry-type plug-in termination by Eaton (PMIC2 range) for connecting 3-core 26/35 kV polymeric cables of 70 mm² to 40.5 kV gas-insulated switchgear through size 2 inner-cone bushings (EN 50180/50181): silicone-rubber stress cone held by a spring set, 1250 A, 117 kV AC withstand, 200 kV impulse; three-phase set with heat-shrink kit; maker's code PMIC2-403x70HS. Used to terminate MV power cables at switchgear, transformers and overhead lines.
- Brand
- Eaton
- Part number
- PMIC2-403x70HS
- Product group
- Cable joints and terminations
- Range
- PMIC2
- Interface
- inner cone size 2 (EN 50181)
- Rated voltage
- 40.5 kV
Request datasheet · No photo yet: ask us for the datasheet or a picture.
Specifications
| Cable rating | 26/35 kV |
|---|---|
| Cable | 3-core polymeric |
| Conductor cross-section | 70 mm² |
| Rated current | 1250 A |
| AC withstand | 117 kV, 5 min |
| Lightning impulse | 200 kV |
| Supplied as | set of 3 phases with heat-shrink kit |
Datasheet, stock and lead time on request. If this part is discontinued or on long lead time we offer an approved equivalent.
More in Cable joints and terminations
- Eaton PMIC2-40P31x240HSInner-cone GIS cable termination, size 2, 1-core, 26/35 kV, 240 mm²
- Eaton PMIC2-40P31x300HSInner-cone GIS cable termination, size 2, 1-core, 26/35 kV, 300 mm²
- Eaton PMIC2-403x50HSInner-cone GIS cable termination, size 2, 3-core, 26/35 kV, 50 mm²
- Eaton PMIC2-403x95HSInner-cone GIS cable termination, size 2, 3-core, 26/35 kV, 95 mm²
- Eaton PMIC2-403x120HSInner-cone GIS cable termination, size 2, 3-core, 26/35 kV, 120 mm²
- Eaton PMIC2-403x150HSInner-cone GIS cable termination, size 2, 3-core, 26/35 kV, 150 mm²