Match the gland to the cable, then to the enclosure, then to the site. 1) Identify the cable construction (unarmoured, SWA/AWA armoured or braided). 2) Measure the cable outer diameter, and for armoured cable also the inner-bedding diameter, and pick the gland size whose seal ranges include both (typically M20 for cables up to about 16 mm, M25 to 26 mm, M32 to 34 mm, M40 to 40 mm, M50 to 53 mm, M63 to 66 mm over the armour). 3) Match the thread form and length to the entry (metric M, NPT or PG). 4) Choose the material for the environment: nickel-plated brass outdoors, 316 stainless steel on the coast or in chemical plants, nylon only indoors or sheltered. 5) In hazardous areas use a gland certified Ex d and/or Ex e for the enclosure’s protection type, with a barrier gland where IEC 60079-14 requires it. 6) Add the accessories: PVC shroud, earth tag, locknut or serrated washer.
Step by step
- Identify the cable constructionRead the cable code or cut face: unarmoured (NYY, H07RN-F, flexible), steel wire armoured (SWA, NYRY), aluminium wire armoured (AWA, single core), or braided (EMC screen, VFD cable). The construction decides the gland family: a single-seal gland for unarmoured cable, an armour-clamping gland (CW type outdoors, BW indoors) for SWA, an EMC gland for braided cable.
- Measure the diametersMeasure the overall outer diameter of the cable with a caliper, and for armoured cable also the diameter over the inner sheath (bedding) under the armour. Use the maker’s cable data sheet when the cable is not yet on site.
- Pick the gland size from the seal rangesEach gland size has a seal range for the outer sheath and, on armoured glands, a second range for the bedding. Both measured diameters must fall inside the ranges, ideally near the middle. Never choose from the conductor size alone: a 4 x 16 mm² SWA cable can need an M25 gland from one maker and an M32 from another.
- Match the thread to the entryMetric ISO threads (M20 x 1.5, M25 x 1.5, M32 x 1.5, M40 x 1.5, M50 x 1.5, M63 x 1.5) are standard in Saudi projects; NPT appears on North American equipment and PG on older German equipment. Use a reducer or adaptor only when it is certified for the installation. Flameproof (Ex d) entries need at least five full threads engaged (IEC 60079-1), so order the long-thread version for thick walls and plates.
- Choose the material and sealing for the siteIndoor dry panels: brass or nylon. Outdoors in Saudi Arabia (ambient above 50 °C, strong UV, sand): nickel-plated brass with a PVC shroud, IP66 and IP68 rated. Coastal plants in Jeddah, Yanbu, Jubail, Ras Al Khair and Rabigh, desalination and chemical areas: 316 stainless steel. Check that the seal elastomer is rated for the site temperature.
- Hazardous areas: match the protection conceptFor Zone 1 and Zone 2 the gland is part of the certified equipment. Use an Ex d gland on flameproof enclosures, an Ex e gland on increased-safety enclosures (most industrial glands are certified Ex db eb for both), with the same gas group and ambient range as the enclosure, and a barrier (compound-filled) gland where IEC 60079-14 asks for one. Unused entries take a certified stopping plug.
- Add the accessories and orderEarth tag (and a bonding lead) for armour earthing or where the enclosure is not metallic, locknut for clearance holes, serrated washer to cut through paint, PVC or LSF shroud outdoors, reducers only where allowed. Order by cable data: construction, outer and bedding diameter, gland thread, material, IP rating and, for Ex, the zone and gas group.
What a cable gland does
A cable gland (also called a cable connector or cord grip) is a mechanical fitting that terminates a cable at an enclosure, motor, luminaire or junction box. It holds the cable against pull-out and twist, seals the entry against dust and water, and on armoured cable clamps the armour and connects it to earth. Glands are specified in IEC 62444 and BS 6121, and for hazardous areas additionally certified to IEC 60079-0 with 60079-1 (Ex d) or 60079-7 (Ex e).
Because the gland is the weak point of an enclosure's IP rating and, in a hazardous area, part of the explosion protection, it is selected as carefully as the enclosure itself.
Step 1: identify the cable construction
The construction of the cable decides the gland family. Unarmoured cables need one seal on the outer sheath; armoured cables need a gland that clamps the armour and seals both the outer sheath and the inner bedding; braided (screened) cables need an EMC gland that bonds the braid 360 degrees.
| Cable | Typical codes | Gland family | Seals |
|---|---|---|---|
| Unarmoured power or control | NYY, N2XY, NYM, H07RN-F, YY, SY (braided), CY | Single-compression gland (brass A2 type, nylon) | Outer sheath |
| Steel wire armoured | SWA, NYRY, NYBY, N2XRY, 0.6/1 kV XLPE/SWA/PVC | Armour-clamping gland: CW (outdoor, double seal), BW (indoor, no outer seal), E1W (with inner seal for Ex) | Outer sheath + inner bedding; armour clamped and earthed |
| Aluminium wire armoured (single core) | AWA, N2XAY | Same CW/E1W family with a non-magnetic (brass or aluminium) body | Outer sheath + bedding |
| Braided or screened | SY, CY, EMC/VFD motor cable | EMC gland with 360-degree braid contact spring | Outer sheath, braid bonded |
| Lead sheathed or MICC | Pb sheath, MI cable | Lead-sheath gland (E1X type) or MICC pot and seal | Sheath |
Step 2: measure the cable and pick the size
The gland size is chosen from two diameters, not from the conductor cross-section: the overall outer diameter of the cable, and on armoured cable the diameter over the inner sheath (bedding) that the inner seal closes on. Both must lie inside the gland's published seal ranges. The table shows typical ranges for metric brass glands; makers differ by a millimetre or two, so the maker's own selection table is the final word.
| Gland size | Entry thread | Unarmoured cable, outer diameter (typical A2 type) | Armoured cable, over armour (typical CW type) | Armoured cable, inner bedding (typical CW type) |
|---|---|---|---|---|
| M20S (20 small) | M20 x 1.5 | 6 to 12 mm | 11.5 to 16 mm | 8.5 to 12 mm |
| M20 | M20 x 1.5 | 9.5 to 16 mm | 14 to 21 mm | 11 to 15.5 mm |
| M25 | M25 x 1.5 | 14 to 20 mm | 19.5 to 26 mm | 15.5 to 20.5 mm |
| M32 | M32 x 1.5 | 18 to 26 mm | 24.5 to 34 mm | 20 to 26.5 mm |
| M40 | M40 x 1.5 | 22 to 32 mm | 32 to 40.5 mm | 26.5 to 32.5 mm |
| M50S / M50 | M50 x 1.5 | 32 to 44 mm | 39.5 to 53 mm | 32.5 to 46.5 mm |
| M63S / M63 | M63 x 1.5 | 44 to 56 mm | 52.5 to 66 mm | 46.5 to 59 mm |
| M75 and above | M75, M90, M100 | Large power cables: select from the maker's table only | ||
Rules of thumb that save returns: a 4 x 16 mm² Cu XLPE/SWA/PVC cable is usually an M25, 4 x 35 mm² an M32, 4 x 95 mm² an M40, 4 x 185 mm² an M50, and 4 x 300 mm² an M63, but the actual diameters on the cable data sheet decide. When a diameter falls on the edge of a range, take the size where it sits nearer the middle of the range, or the smaller size when the seal must grip firmly against pull.
Step 3: thread type and length
The gland thread must match the enclosure entry: metric ISO (IEC 60423: M20 x 1.5, M25 x 1.5, M32 x 1.5, M40 x 1.5, M50 x 1.5, M63 x 1.5) is standard on IEC equipment and Saudi projects, NPT (1/2", 3/4", 1", 1 1/4", 1 1/2", 2") is standard on North American and some oil-and-gas equipment, and PG (PG 13.5, PG 16, PG 21) appears on older German machinery.
- Thread length: standard glands have about 15 mm of thread; a long-thread version (around 25 to 30 mm) is needed for thick cast walls, gland plates with gaskets and flameproof entries, where at least five full threads must be engaged (IEC 60079-1).
- Adaptors and reducers: change the entry size or thread form (M25 to M20, NPT to metric). In hazardous areas they must be certified and limited to one adaptor per entry.
- Clearance holes (unthreaded plates) need a locknut and, on painted plates, a serrated washer or earth tag for electrical continuity.
Step 4: material, plating and sealing
The gland material decides how long the seal and the earth path last in the site's climate. In Saudi Arabia the three enemies are heat (ambient above 50 °C on the surface of outdoor panels), ultraviolet light and salt-laden, sandy air on the coasts.
| Material | Where it suits | Saudi notes |
|---|---|---|
| Brass (plain) | Indoor panels, dry plant rooms | Tarnishes outdoors; fine inside air-conditioned switchrooms |
| Nickel-plated brass | Outdoor, industrial, most Ex glands | The default for Saudi outdoor installations; add a PVC shroud against sand and UV |
| Stainless steel 316 / 316L | Coastal, desalination, chemical, food and pharma wash-down | Jeddah, Yanbu, Jubail, Ras Al Khair and Rabigh plants; also where chlorides or acids are present |
| Aluminium | Light-weight, aluminium enclosures, single-core AWA cables (non-magnetic) | Avoid in marine salt spray unless specified; isolate from copper earth bars |
| Nylon (polyamide PA66) | Unarmoured cables indoors, light duty, instrumentation | Only UV-stabilised black outdoors, and never for armoured cable; check the temperature rating |
IP66 or IP68? IP66 means dust-tight and protected against powerful water jets; IP68 means protected against continuous immersion to the depth and time the maker states (for glands often 100 m for seven days). For outdoor panels, wash-down areas and buried pits specify both, IP66 and IP68, and check the seal temperature range: standard seals cover about −20 to +80 °C continuous, silicone seals go higher.
Step 5: hazardous areas (Ex d, Ex e, ATEX, IECEx)
In a hazardous area the gland is part of the certified equipment: it must carry its own Ex certificate (ATEX and/or IECEx) for the protection concept of the enclosure, the gas group and the ambient temperature range. An Ex d (flameproof) gland is used on flameproof enclosures and an Ex e (increased safety) gland on increased-safety enclosures; most industrial Ex glands are certified Ex db eb IIC Gb and Ex tb IIIC Db, so one gland covers both and dust.
- Barrier glands (filled with a setting compound around the cores) are required by IEC 60079-14 on flameproof enclosures in cases such as an internal source of ignition with a cable that is not substantially compact and circular, or gas group IIC installations; the project specification normally states when.
- Unused entries must be closed with certified stopping plugs of the same protection concept.
- Earthing: the armour must be earthed at the gland (earth tag or the enclosure's earth), and the gland body must maintain continuity through painted plates.
- Ambient: standard certification covers −20 to +40 °C; outdoor Saudi plants often specify +55 or +60 °C, so order glands with the wider marked range (Ta).
Our hazardous-area equipment guide explains zones, EPLs, gas groups and how to read an Ex marking.
Step 6: accessories
- Shroud (PVC or LSF): covers the gland nut and cable entry against sand, dust, UV and dripping water; standard on Saudi outdoor installations.
- Earth tag: a brass or stainless plate under the gland to bond the armour to the earth bar; use it on non-metallic enclosures or where the enclosure earth is not reliable.
- Locknut: secures the gland in a clearance hole; brass or nickel-plated to match the gland.
- Serrated washer: bites through paint to give electrical continuity between gland and plate.
- Entry thread sealing washer or IP washer: keeps the IP rating at the gland-to-plate joint.
- Reducers, adaptors and stopping plugs: as above; certified for Ex where used in hazardous areas.
Worked example: a feeder in Jubail
Cable: 4 x 25 mm² Cu XLPE/PVC/SWA/PVC 0.6/1 kV, outdoor, to a nickel-plated steel motor control panel on an open gland plate in a Zone 2 (IIA, T3) area of a petrochemical plant in Jubail Industrial City.
- Construction: steel wire armoured, so an armour-clamping gland with a double seal (CW type).
- Diameters from the cable data sheet: outer 24.2 mm, over bedding 19.6 mm. Both fall inside the M25 ranges (19.5 to 26 mm over armour, 15.5 to 20.5 mm bedding) and near the middle, so M25, not M32.
- Thread: M25 x 1.5 into a gland plate with a gasket: standard thread length, with a locknut.
- Site: coastal, salt-laden air and 50 °C ambient: 316 stainless steel body (nickel-plated brass is acceptable if the specification allows), IP66/IP68, seal rated to at least +80 °C.
- Zone 2: gland certified Ex db eb IIC Gb / Ex tb IIIC Db, Ta range to +60 °C, no barrier required for Zone 2 with a compact cable (confirm against IEC 60079-14 and the project specification).
- Accessories: LSF shroud, earth tag with 16 mm² bonding lead, serrated washer, certified stopping plugs for the two spare entries.
Ordering line: "Cable gland M25, CW type, 316 SS, Ex db eb IIC Gb, IP66/68, for SWA cable OD 24.2 / bedding 19.6 mm, with LSF shroud, earth tag, locknut and serrated washer."
Comparison: common gland types
| Type | Cable | Seals | Location | Typical material |
|---|---|---|---|---|
| A2 (single compression) | Unarmoured | Outer sheath | Indoor and outdoor | Brass, nickel-plated brass, 316 SS, nylon |
| BW | SWA | None (armour clamp only) | Indoor, dry | Brass |
| CW | SWA, AWA | Outer sheath + bedding | Outdoor, industrial | Nickel-plated brass, 316 SS |
| E1W / E1FW | SWA, AWA, braided | Outer + inner, Ex certified | Hazardous areas | Nickel-plated brass, 316 SS |
| Barrier (compound) | Any, flameproof entries | Compound around cores + outer | Ex d where IEC 60079-14 requires | Nickel-plated brass, 316 SS |
| EMC | Braided, screened | Outer sheath, braid bonded | Drives, instrumentation | Nickel-plated brass |
| Nylon | Unarmoured, flexible | Outer sheath | Indoor, light outdoor (UV grade) | PA66 |
What to send us for a quotation
The cable construction and size (for example 4 x 25 mm² Cu XLPE/SWA/PVC), its outer and bedding diameters or the cable data sheet, the entry thread and plate thickness, indoor or outdoor, the material, the IP rating, and for hazardous areas the zone, gas group and ambient temperature. Send the quantities per size and we quote certified glands with their accessories, datasheets and certificates, usually within 24 hours. Our cable gland selector gives a first answer from the cable diameter and location.
Common questions
What size cable gland do I need for a 4-core 16 mm² SWA cable?
Usually an M25, but the gland size is chosen from the cable’s outer diameter and inner-bedding diameter, not from the conductor size. A 4 x 16 mm² Cu XLPE/SWA/PVC cable is typically about 20 to 22 mm over the armour and 16 to 17 mm over the bedding, which falls in the M25 ranges of most makers; check the cable data sheet against the gland table.
What is the difference between BW and CW cable glands?
Both clamp steel wire armour. A BW gland has no seals and is for dry indoor use; a CW gland adds an outer seal on the sheath and an inner seal on the bedding, so it is weatherproof (IP66/IP68) and is the type used outdoors and in industrial plants.
Is IP68 better than IP66 for a cable gland?
They test different things. IP66 is protection against powerful water jets, IP68 against continuous immersion to a stated depth and time. Outdoor glands in Saudi Arabia should carry both, and the seal temperature range matters as much as the IP code.
Brass, nickel-plated brass or stainless steel in Jeddah?
Nickel-plated brass with a PVC shroud is the standard outdoor choice in Saudi Arabia. Within reach of sea air (Jeddah, Yanbu, Jubail, Ras Al Khair, Rabigh), in desalination and chemical plants, 316 stainless steel lasts longer and is usually specified. Plain brass is for indoor, dry panels.
Can I use a nylon cable gland outdoors in Saudi Arabia?
Only a UV-stabilised black polyamide gland for unarmoured cable, in a sheltered position, and within its temperature rating; direct sun on a panel in summer can exceed 70 °C at the gland. For exposed, armoured or hazardous-area installations use metal glands.
Do I need an earth tag on every gland?
Not on every gland. The armour must be earthed, which a metal gland in a metal enclosure achieves through the enclosure; an earth tag is needed on non-metallic enclosures, painted plates without a serrated washer, and wherever the specification calls for a visible bond.
When is a barrier gland required?
IEC 60079-14 requires a barrier (compound-filled) gland on flameproof (Ex d) enclosures in defined cases, for example an enclosure with an internal source of ignition and a cable that is not substantially compact and circular, or some gas group IIC installations. Most Zone 2 and Ex e installations use standard Ex db eb glands.
Can I use a reducer to fit a smaller gland in a larger entry?
Yes in industrial areas, with a reducer of the same material and IP rating. In hazardous areas the reducer must be certified, only one adaptor is allowed per entry, and the five-thread engagement rule still applies to flameproof enclosures.
Need these items? Send your list or a nameplate photo; your quotation arrives within 24 hours.
This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.