Ex cable glands
Hawke CSB 656
CSB 656 compound barrier cable gland, Ex d/Ex e II 2GD, M20-M100
Compound-filled barrier gland that seals the individual cores of a cable or conduit at the enclosure entry; a two-part compound and instructions come with it. The compound chamber can be separated to check the fill, and a female coupler takes a gland or conduit.
- Brand
- Hawke
- Part number
- CSB 656
- Product group
- Ex cable glands
- Range
- CSB 656
- Type
- Compound barrier cable gland with female running coupler
- Protection
- Ex d / Ex e, II 2 GD (ATEX)
Request datasheet · No photo yet: ask us for the datasheet or a picture.
Specifications
| Certificate | BAS 01 ATEX 2082X |
|---|---|
| Gas groups | IIA, IIB, IIC |
| Zones | 1, 2, 21, 22 |
| Ingress protection | IP66, IP67, IP68 (30 m for 7 days), NEMA 4X |
| Standards | EN 50014, EN 50018, EN 50019, EN 50281-1-1, IEC 60079-0, IEC 60079-1, IEC 60079-7 |
| Materials | Brass (standard), stainless steel, aluminium; NPT entries nickel plated |
| Thread | Metric 1.5 mm pitch; NPT option |
| Deluge protection | DTS01 |
| Sizes (max over cores / max inner sheath / max cores) | A M20 11.0/12.5 mm/10; B M25 16.2/18.4/21; C M32 21.9/24.7/42; C2 M40 26.3/29.7/60; D M50 37.1/41.7/80; E M63 47.8/53.5/100; F M75 59.0/66.2/120; G M80 62.8/74.0/140; H M90 70.9/83.0/160; J M100 80.3/93.0/180 |
| Ordering | CSB 656/C/M32/M32 (size/male thread/female thread) |
Datasheet, stock and lead time on request. If this part is discontinued or on long lead time we offer an approved equivalent.
More in Ex cable glands
- Hawke 711711 explosion-proof cable gland/connector, cULus, Class I Division 1 Groups A, B, C, D
- Hawke 753753 explosion-proof cable gland/connector, cULus, Class I Division 1 Groups A, B, C, D
- Hawke 755755 explosion-proof cable gland/connector, cULus, Class I Division 2 Groups A, B, C, D
- Hawke SB 474SB 474 barrier cable gland with female coupler, Ex d/Ex e II 2GD, M20-M32
- Helukabel 906691Ex cable gland HELUTOP HT-PA-EX, Ex e, polyamide, M20 x 1.5, cable 6–12 mm
- Helukabel 906692Ex cable gland HELUTOP HT-PA-EX, Ex e, polyamide, M20 x 1.5, cable 10–14 mm