Cable derating in Gulf heat: ambient temperature correction factors and how to apply them

The current ratings in cable tables are worked out for mild conditions. In Saudi Arabia and the Gulf, air in summer, the sun on cable trays and cables grouped close together all reduce how much current a cable can carry safely. This guide shows the correction factors from IEC 60364-5-52 and how to use them.

By the Six Winds engineering team · Updated

Quick answer

Cable current ratings in IEC 60364-5-52 assume 30 °C air or 20 °C ground. At 50 °C air, multiply the tabulated rating by 0.71 for PVC (70 °C) insulation or 0.82 for XLPE (90 °C) insulation, then apply the grouping factor from the same standard. A cable rated 100 A at 30 °C in PVC carries only 71 A at 50 °C.

Step by step

  1. Set the design temperaturesTake the design air temperature and, for buried cables, the ground temperature from the project specification. Use the hottest conditions the cable will see, not the yearly average.
  2. Read the tabulated ratingFrom IEC 60364-5-52 or the maker's data, take the current rating for the cable type, insulation and installation method. It is valid for 30 °C air or 20 °C ground.
  3. Apply the temperature factorMultiply by the ambient correction factor for the insulation: for 50 °C air, 0.71 for PVC and 0.82 for XLPE. Use the ground temperature table for buried cables.
  4. Apply the grouping factorMultiply again by the grouping factor from the same standard for the number of circuits and the way they are laid. Allow for direct sun on exposed trays as the specification requires.
  5. Compare with the protective deviceThe corrected rating Iz must be at least the rated current In of the breaker or fuse. If it is not, choose a larger cable.
  6. Check voltage drop and short circuitCheck the voltage drop over the full length and the short-circuit withstand. Use our cable-size calculator, then confirm with the maker's data.

Why the table rating is not your rating

The current rating of a cable is the current at which its conductor reaches the maximum temperature of its insulation: 70 °C for PVC and 90 °C for XLPE or EPR in normal use. The hotter the surroundings, the less heat the cable can shed, and the lower the current it can carry.

The tables in IEC 60364-5-52 are based on an ambient of 30 °C for cables in air and 20 °C for cables in the ground. Gulf summer temperatures are well above these, and air inside trenches, ducts, ceiling voids and plant rooms can be hotter still. The design ambient for each project is set in its specification; use that value, and when in doubt use the hottest condition along the route.

Ambient air temperature correction factors

IEC 60364-5-52, Table B.52.14 gives the factors for air temperatures other than 30 °C. Multiply the tabulated current rating by the factor:

Ambient air temperaturePVC insulation (70 °C)XLPE or EPR insulation (90 °C)
30 °C (table reference)1.001.00
35 °C0.940.96
40 °C0.870.91
45 °C0.790.87
50 °C0.710.82
55 °C0.610.76

Buried cables use a separate table in the same standard for ground temperatures other than 20 °C, and a correction for soil thermal resistivity. Dry desert sand conducts heat poorly, so take the soil value from the site survey or the specification.

Grouping, sun and enclosed runs

Temperature is not the only correction. Cables laid together heat each other, so IEC 60364-5-52 gives grouping factors by the number of loaded circuits and the arrangement: bunched, in a single layer, on perforated trays or ladders, touching or spaced. Apply the grouping factor from the same standard on top of the temperature factor; on a full tray the combined reduction is large.

Direct sun adds heat that the tables do not include. Trays and cables exposed to the sun run hotter than the shade air temperature. Shade the cables with tray covers or sun shields where possible, or allow for solar radiation in the rating as the project specification requires; the IEC 60287 rating methods include a term for it. Cables in conduits, closed trunking or ducts also have lower ratings than cables in free air, so use the rating for the actual installation method.

Why XLPE and UV-resistant sheaths are common in KSA

XLPE insulation is rated for 90 °C in normal use and 250 °C during a short circuit, against 70 °C and 160 °C for PVC (for most sizes). In a hot ambient this matters twice: XLPE cables have higher tabulated ratings for the same size, and they lose less of that rating as the temperature rises (0.82 at 50 °C against 0.71 for PVC). The result is often a smaller cable for the same load, which is why XLPE power cables such as N2XY and armoured N2XRY or N2XSRY are widely specified in Saudi projects.

The outer sheath also needs to suit the sun. Cables run outdoors should have a sheath that the maker states is UV-resistant, typically black, carbon-black-stabilised PVC or PE. For buildings where smoke and halogen gases are a concern, the specification may call for LSZH sheaths; check that the maker confirms UV resistance if those cables will be in the sun.

Worked example and voltage drop

A cable with a tabulated rating of 100 A at 30 °C, PVC insulated, installed in 50 °C air:

Corrected rating = 100 A × 0.71 = 71 A

The same size with XLPE insulation and the same tabulated 100 A would give 100 × 0.82 = 82 A. If the cable is also grouped with other circuits, multiply again by the grouping factor. The other way round: to protect a circuit with a 63 A breaker in 50 °C air, the PVC cable needs a tabulated rating of at least 63 ÷ 0.71 ≈ 89 A before grouping.

Voltage drop rises with the length of the run and with the current, and a hot conductor has a higher resistance (copper rises by about 0.4 % per °C), so long runs in hot plants often need a larger size than the current rating alone would give. Check the drop over the full route against the limit in the specification. Our cable-size calculator does the temperature, grouping and voltage-drop checks together; confirm the final size against the maker's data.

Common questions

What temperature are cable current tables based on?

IEC 60364-5-52 tables assume 30 °C air for cables in air and 20 °C ground for buried cables. Other conditions need correction factors from the same standard.

What is the derating factor for PVC cable at 50 °C?

0.71, from IEC 60364-5-52 Table B.52.14 for PVC (70 °C) insulation. For XLPE (90 °C) insulation at 50 °C the factor is 0.82.

Do I apply both temperature and grouping factors?

Yes. Multiply the tabulated rating by the ambient temperature factor and then by the grouping factor for the number of circuits and how they are laid.

Does direct sunlight reduce cable rating?

Yes. Cables in the sun run hotter than the shade air temperature. Shade them with tray covers or allow for solar radiation as the project specification requires.

Why is XLPE cable preferred in hot climates?

XLPE is rated for 90 °C against 70 °C for PVC, so it carries more current for the same size and loses less of its rating as the ambient rises.

Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.

This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.