Read every rating together with its conditions: the standard it was tested to, the voltage, the ambient temperature and the installation method. Then check the derating notes for your site, the IP and IK ratings, the dimensions and mounting, and decode the full ordering code, because one character can change the product.
Step by step
- Find the standard and the conditionsNote which IEC or EN standard the product is tested to and the reference conditions: voltage, ambient temperature, installation method and duty. Ratings only mean something against these.
- Separate rated values from nominal valuesRated values are what the maker guarantees under the stated conditions. Nominal values only name the system or size. Compare rated values with your design.
- Apply the derating notesLook for the tables or footnotes that reduce the rating for higher ambient temperature, grouping, altitude, mounting position or enclosure. Use your site values, not the reference ones.
- Check protection, size and mountingConfirm the IP and IK ratings, the dimensions, the mounting method, the terminal capacity and the cable entries against the panel or site.
- Decode the ordering codeBreak the part number into its parts: base type, rating, poles, voltage or coil voltage, options. Make sure every character matches what you need.
- Check the certificatesAsk for the certificates the specification requires and check that they cover the exact part number and standard, not only the product family.
Rated values and nominal values
A rated value is assigned by the maker for stated conditions and backed by tests to the product standard: rated current In, rated operational voltage Ue, rated insulation voltage Ui, rated impulse withstand voltage Uimp, rated breaking capacity. A nominal value names the system or the size: a 400 V network, a 16 mm² cable, a 100 W luminaire. Nominal values help you find the product; rated values tell you whether it suits the job.
Some ratings come in sets. A contactor has a different current for AC-1 (resistive loads) and AC-3 (motors started direct on line) under IEC 60947-4-1, and a different value at each voltage. A cable's current rating is given for one installation method and one ambient temperature. Always read the row that matches your use.
Datasheet field, what it means, what to check
| Datasheet field | What it means | What to check |
|---|---|---|
| Rated current In / Ie | Current the product carries continuously under the stated conditions | The reference ambient and, for contactors, the utilisation category (AC-1, AC-3) at your voltage |
| Ue, Ui, Uimp | Operating voltage, insulation voltage, impulse withstand voltage | Ue at least your system voltage; Uimp suits the overvoltage category of the installation |
| Breaking capacity (Icn, Icu, Ics) | Largest fault current a breaker interrupts safely | The value at your voltage is at least the prospective fault current |
| Cable Uo/U and conductor class | Voltage grade (for example 0.6/1 kV) and conductor build to IEC 60228 | Grade and class match the specification; class 5 for flexible cords |
| Maximum conductor temperature | 70 °C for PVC, 90 °C for XLPE in normal use | The current rating you use belongs to the same insulation and method |
| Ambient temperature range | Air temperature the product is rated to work in (Ta for luminaires) | Covers the real panel or site temperature in summer |
| IP and IK rating | Protection against dust and water (IEC 60529) and against impact (IEC 62262) | Suits the location; the rating applies with the stated glands and gaskets fitted |
| Luminous flux and efficacy | Light output (lm) and lm/W of the complete luminaire | Luminaire values, not LED chip values; the test temperature stated |
| Lifetime (L70, L80, B10) | Hours until light output falls to the stated share | The ambient temperature at which the claim is made |
| Coil voltage Uc | Control voltage of a contactor or relay coil, AC or DC | Matches the control circuit exactly |
| Terminal capacity and torque | Cable sizes the terminals accept and the tightening torque | Your cable size fits; lugs or ferrules needed |
| Ordering code | Part number built from type, rating and options | Every character decoded; accessories ordered separately where stated |
Standards and certificates listed
The datasheet usually lists the product standard (for example IEC 60898-1 or IEC 60947-2 for breakers, IEC 60947-4-1 for contactors, IEC 60502-1 for 0.6/1 kV power cables, IEC 60598 for luminaires) and the marks or certificates the product carries. Read these with care:
- A standard number on the datasheet is the maker's declaration. Third-party test reports or certificates (for example a CB test certificate or a certificate from an independent test laboratory) are stronger evidence, and many specifications ask for them.
- Check that the certificate names the exact part number or range, and the edition of the standard the specification asks for.
- Cable fire performance is listed separately: IEC 60332-1 for flame spread on a single cable, IEC 60332-3 for bunched cables, IEC 61034 for smoke density and IEC 60754 for halogen and acid gas. "LSZH" or "halogen-free" claims should point to these tests.
- For Saudi Arabia, products under a SASO technical regulation need a SABER conformity certificate. Equipment for hazardous areas needs an IECEx or ATEX certificate with the zone, gas group and temperature class.
Derating notes and ambient temperature
Ratings are given at reference conditions that are cooler than many Saudi sites. MCBs to IEC 60898-1 are calibrated at 30 °C, many MCCBs at 40 °C, and cable current ratings in IEC 60364-5-52 assume 30 °C air or 20 °C ground. Look for the derating tables or footnotes that cover:
- higher ambient temperature, inside a panel or outdoors in summer;
- several devices mounted side by side, or cables grouped on a tray;
- altitude above 2000 m, where IEC 60947-1 asks for derating;
- mounting position other than the one tested, for example horizontal mounting of a vertical device;
- a luminaire or driver run near the top of its Ta range, which shortens its life.
If the datasheet gives no derating for your conditions, ask the maker for it in writing before you approve the product.
Dimensions, mounting and the part number
The dimensional drawing tells you if the product fits: width in modules (one module is 18 mm on DIN-rail devices), depth behind the door, cut-out size, fixing centres and the space the maker requires around the device for heat and arc gases. Check the mounting (35 mm DIN rail to IEC 60715, base plate, plug-in or draw-out), the cable entry and the terminal type.
The ordering code is a short form of all these choices. It is usually built as a base type followed by codes for rating, poles, breaking capacity, trip unit or coil voltage, and options. Two codes can differ by one character and be very different products, for example the same contactor with a 24 V DC coil and a 230 V AC coil. Decode the full code from the maker's ordering table, and note which accessories are ordered as separate items.
Before you approve an equivalent
An equivalent from another maker can be accepted when it matches the specified product where it matters, not only on the main rating:
- Same or better rated values at your conditions: current, voltage, breaking capacity, utilisation category, IP and IK.
- Tested to the same standard, with the certificates the specification asks for.
- Fits the space, mounting, terminals and cable entries without changes to the panel or site.
- Coordination still works: selectivity with the upstream breaker, type 2 coordination of a motor starter, accessories that suit the new frame.
- Datasheet, certificates and the consultant's approval on file before installation.
On our quotations an alternative is always marked as such, with the maker, the part number and the datasheet, so your engineer can check it. E-mail sales@sixwinds.com.sa or use the quotation form.
Common questions
What is the difference between rated and nominal values?
A rated value is guaranteed by the maker under stated test conditions, such as rated current at a given ambient. A nominal value only names the system or size, such as a 400 V network or a 16 mm² cable.
Why does a contactor have two current ratings?
IEC 60947-4-1 rates contactors by utilisation category. AC-1 covers resistive loads and gives a higher current; AC-3 covers motors started direct on line and gives a lower current for the same contactor.
Is a standard number on a datasheet enough proof of compliance?
It is the maker's declaration. Where the specification asks for it, request a third-party test report or certificate that names the exact part number and the edition of the standard.
What ambient temperature are cable ratings based on?
The current ratings in IEC 60364-5-52 assume 30 °C air for cables in air and 20 °C ground for buried cables. At higher temperatures, apply the correction factors from the same standard.
What should match when I accept an equivalent product?
Rated values at your conditions, the test standard and certificates, dimensions and mounting, and coordination with the devices around it. The consultant's approval should be on file before installation.
Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.
This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.