Start from the area classification (zone, gas or dust group, temperature class), then choose the luminaire type for the task, check the rated ambient temperature for Saudi heat, and ask for the certificate and photometric data of the exact model offered. Watts and IP rating alone never prove a light is suitable.
Step by step
- Get the area classificationAsk for the hazardous area drawing and the approved specification: zone, gas or dust group and temperature class for each location.
- Turn the zone into a protection levelZone 1 needs EPL Gb, Zone 2 needs Gc, Zone 21 needs Db and Zone 22 needs Dc, or better.
- Choose the luminaire type for the taskFloodlight for areas, high bay for high structures, linear for walkways and pipe racks, bulkhead for low local light, hand lamp for inspection.
- Check Saudi site conditionsRated ambient (Ta) for the hottest day in the sun, dust, humidity, salt, vibration and access for maintenance.
- Size the lightWork from lux and lumens, not watts, and ask for the photometric file of the offered model.
- Check the documentsCertificate and schedule for the exact model and options, marking, instructions, photometrics and a compliance sheet.
- Compare quotations line by lineSame model, quantity, optics, voltage, accessories, glands, documents, warranty and delivery in every offer.
What does explosion-proof lighting mean?
"Explosion-proof light" is a trade name for luminaires certified for use where flammable gas, vapour or combustible dust may be present. Behind the name there are several protection methods: flameproof enclosures (Ex d), increased safety (Ex e), encapsulation (Ex m), dust protection by enclosure (Ex t) and others. Each is certified for particular zones, gas or dust groups and temperature classes.
So the name alone tells you very little. Suitability is shown by the Ex marking on the nameplate and the certificate of that exact model, together with its rated ambient temperature and installation conditions. Ask for those, not for "heavy duty" or "industrial" wording.
Start from the area classification
The area classification drawing comes from the project's process or HSE team. For every location it gives the zone and the gas or dust data. Convert the zone into the minimum equipment protection level (EPL):
| Atmosphere | Zone | Present… | Minimum EPL |
|---|---|---|---|
| Gas, vapour, mist | 0 / 1 / 2 | continuously / likely in normal operation / rarely and briefly | Ga / Gb / Gc |
| Combustible dust | 20 / 21 / 22 | continuously / likely in normal operation / rarely and briefly | Da / Db / Dc |
The zone is not the only check. Also match:
- Gas group IIA, IIB or IIC (IIC covers all three) or dust group IIIA, IIIB or IIIC.
- Temperature class (T1 to T6) for gas, or the maximum surface temperature in °C for dust, against the ignition temperatures on site.
- The rated ambient temperature range (Ta) and any special conditions (an "X" after the certificate number).
A luminaire approved for gas is not automatically approved for dust. Where both are present, it must carry both markings. Very few luminaires are made for Zone 0 or 20; light those areas from outside the zone where you can.
Our explosion-proof lighting selector turns the zone, group and temperature class into the marking to ask for, and the hazardous area quick guide explains each part of an Ex marking.
Which type of explosion-proof luminaire?
Choose the shape of the luminaire by the lighting task, then check that the model suits the classified area.
| Type | Typical use | What to compare |
|---|---|---|
| Floodlight | Process areas, yards, loading bays, tank farms | Beam and aiming, area covered, glare, mounting bracket |
| High bay | Shelters, compressor houses, high structures | Mounting height, spacing, obstructions, access for maintenance |
| Linear | Walkways, pipe racks, platforms, along equipment | Light spread along the route, mounting method, length |
| Bulkhead / well-glass | Stairs, doors, local light at low height | Guard, glass, mounting surface, cable entry |
| Hand lamp | Inspection and maintenance inside vessels and pits | Battery or mains, voltage, cable length, weight, hanging |
Our own range covers explosion-proof floodlights, high bays, linear lights and bulkheads; see all on the explosion-proof lighting page.
When to choose each type
- Floodlight: when light must be aimed to cover a defined area. Send the area size, the mounting height and the possible mounting points, and ask for the photometric distribution of the offered model so the layout can be calculated.
- High bay: when light comes from a height. Spacing, obstructions and the uniformity on the floor matter more than the wattage; a higher wattage does not prove the coverage.
- Linear: when light must follow a walkway, a ladder or a line of equipment. State the mounting (surface, pendant, pole, bracket) and any accessories.
- Hand lamp: "portable" does not always mean rechargeable. Mains hand lamps usually run at 24 V or 50 V from an isolating transformer kept outside the hazardous area.
Is IP66 the same as explosion-proof?
No. The IP rating says how well the enclosure keeps out dust and water (IP66: dust-tight and protected against powerful water jets). Explosion protection is a separate assessment with its own marking and certificate. A good Ex luminaire usually has both, but each describes something different.
Never replace a certified Ex luminaire with an ordinary outdoor floodlight because the IP rating is the same.
Saudi site conditions to state
A request for a light "suitable for Saudi conditions" leaves the supplier guessing. State what the site really has:
- Heat: the hottest air temperature, and whether the luminaire is in direct sun. Many Ex luminaires are rated to +40 °C as standard; outdoor plants in the Kingdom usually need +50 to +60 °C. Check the Ta range on the nameplate, and that the certificate covers it.
- Dust and sand: IP66 or better, and a maintenance factor that allows for dirt on the glass.
- Salt and humidity: on the Gulf and Red Sea coasts and offshore, ask for a marine-grade coating (C5M class) and 316 stainless hardware. See our marine floodlights for the same logic outside hazardous areas.
- Vibration near compressors and pumps, and the mounting surface.
- Access: how often the light can be reached for inspection; long-life LED and a good driver reduce work-at-height permits.
Ask the supplier to confirm the model suits these conditions and to state any limits.
Size the light: lumens, not watts
Watts show the power drawn; lumens show the light produced. The lux on the working plane depends on the lumens, the optic, the mounting height and the obstructions. A quick first estimate uses the lumen method:
Lumens needed ≈ lux × area ÷ (utilisation factor × maintenance factor)
Example (assumed values): a 30 m × 20 m outdoor process area at 150 lx, utilisation 0.4 and maintenance factor 0.7 needs about 150 × 600 ÷ 0.28 ≈ 321,000 lm, so around 25 floodlights of 13,000 lm. A photometric calculation with the offered luminaire then confirms the layout and uniformity. Our selector makes this estimate for you.
Documents to check before you buy
Ask for a technical submittal that links the offered product to the project requirements:
| Document | Why |
|---|---|
| Datasheet and order code | Identifies the exact model and options offered |
| Ex marking and nameplate | Compare the protection, group, T-class and Ta with the requirement |
| IECEx / ATEX certificate and schedule | Confirms what is covered, and any special conditions ("X") |
| Installation and maintenance instructions | Permitted mounting, cable entries, opening and servicing |
| Drawings and accessory list | Scope of supply, brackets, glands and stopping plugs |
| Photometric file | Lighting calculations and layout |
| Compliance sheet | Clause-by-clause compliance, exceptions and alternatives |
If the specification asks for IECEx or ATEX, check that the documents cover the exact model and configuration offered. A certificate for one component (a driver or a gland) does not certify the whole luminaire.
Print the Ex marking decoder
Keep a one-page chart next to the nameplates you check: it reads a marking such as II 2 G Ex db eb IIC T4 Gb part by part, with the protection types, gas and dust groups, temperature classes, zones and their US Class/Division equivalents.
Download the Ex marking decoder (A4 PDF)
How to compare quotations
Make the requirements the same for every supplier first, then compare prices. Every offer should state:
- model and quantity; wattage, lumens and optic;
- voltage and control or dimming;
- brackets, cable entries, Ex glands and stopping plugs;
- documents and inspections included;
- warranty, delivery time, and what is included or excluded.
Ask for options such as dimming or an emergency version to be priced separately. Do not assume that the catalogue photo shows every part of the offer.
What to send for a quotation
- Project location and use of the area.
- Area classification and the approved specification.
- Luminaire types and quantities, or the area size and mounting height for us to estimate.
- Supply voltage and control requirements.
- Site conditions and required accessories.
- Mandatory documents and the delivery date.
For replacements, add the data of the existing fittings and any limits on cabling, mounting or access. The selector builds this summary in one click and sends it to our engineers.
Common questions
What is the best explosion-proof light for a factory?
There is no single best model. The choice follows the zone and gas or dust data of the location, the lighting task and the site conditions, and then the documents of the exact model offered.
Does every industrial site need explosion-proof lights?
No. Only locations classified as hazardous areas need Ex equipment. Check the area classification drawing and risk assessment, not the word industrial.
Should I choose by watts or by lumens?
Look at both, but size the lighting by lux and lumens. Watts show the power drawn; the light that reaches the work also depends on the optic, height and obstructions.
Are explosion-proof lights available with an emergency battery?
Some models are. Confirm the emergency light output and duration, the temperature limits of the battery version and that its certificate covers it.
Is a certified component enough to approve the luminaire?
No. The certificate must cover the complete luminaire in the configuration offered, not just one component.
What ambient temperature should I ask for in Saudi Arabia?
For outdoor plants, usually at least +50 °C and often +55 to +60 °C in direct sun. Use the project specification and check the Ta range on the nameplate.
Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.
This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.