Marechal DECONTACTOR switch-rated plugs and sockets: the built-in switch, AC-22A/AC-23A ratings and the DSN and DS ranges

A DECONTACTOR is a Marechal plug and socket-outlet with a load-break switch built into the socket. It lets an operator connect and disconnect a motor or machine while it is running, without a separate switch or a pilot-wired contactor, and it doubles as a local isolation point next to the machine that can be padlocked.

By the Six Winds engineering team · Updated

Quick answer

Choose a DECONTACTOR when the plug will be pulled with the load on, or when the socket is the local isolator for a motor. Pick the range from the current and from the switching rating at your voltage (AC-23A for motors), then GRP or metal, IP rating, poles and voltage coding, and add a wall box, sleeve or handle for every socket-outlet and inlet.

Step by step

  1. Name the loadHeaters and lighting are resistive or mixed loads (AC-21A, AC-22A). Motors, pumps, fans and compressors are motor loads (AC-23A). DC circuits use DC-21A. The category decides which current rating applies.
  2. Read the switching rating at your voltageA DECONTACTOR has a connector rating and a switching rating, and the switching rating can drop at higher voltage. A DSN6 carries 63 A and breaks 63 A of motor load at 400 V, but 40 A of mixed load at 690 V.
  3. Pick the rangeDSN1, DSN3 and DSN6 cover 16 to 63 A in GRP or metal with IP66/IP67/IP69. DS1, DS3, DS6, DS9 and DS2 run from 16 to 250 A and up to 1000 V AC.
  4. Choose poles and voltage coding2P, 1P+N+E, 3P+E or 3P+N+E, plus the voltage and frequency. The coding key stops a plug entering a socket wired for a different voltage.
  5. Choose the mountingEvery socket-outlet and inlet needs a wall box, an inclined sleeve or a handle. A socket-outlet on a handle becomes an in-line connector for an extension cable.
  6. Add the optionsPadlocking pin, inlet cap, self-closing lid, auxiliary or pilot contacts, a black housing, or antibacterial handles for food areas.

What a DECONTACTOR is

Inside a DECONTACTOR socket-outlet is a switch rated to make and break load current. The plug engages the socket, the switch closes the circuit, and pressing the release button opens the switch: the current is cut inside the socket and the plug is already dead when it comes out. Marechal builds the range to IEC/EN 60309-1 and 60309-4 (the part covering switched socket-outlets), and the breaking capacity is tested to IEC/EN 60947-3, the switch-disconnector standard.

The contacts are spring-loaded butt contacts with silver-nickel tips rather than pins and sleeves, and the terminals are spring-assisted so they stay tight under vibration and heat cycles. On connection the earth makes first, then neutral, phases and finally auxiliary or pilot contacts; on disconnection they open in the reverse order. A safety shutter covers the socket contacts so they cannot be reached with a finger or a 1 mm wire.

Why it is safer than a standard CEE plug

A standard IEC 60309-2 (CEE) pin-and-sleeve plug is a connector, not a switch: pulling it under load draws an arc at the pins. For larger ratings it is therefore paired with a separate switch or interlock ahead of the socket. A DECONTACTOR puts that switch inside the socket, so the same device connects, disconnects under load, isolates the machine for maintenance and can be locked off.

Standard CEE plug (IEC 60309-2)Marechal DECONTACTOR
Current ratings16, 32, 63, 125 A16, 20, 30, 32, 50, 63, 90, 100, 150, 250 A
Built-in load-break switchNoYes (IEC 60309-4, breaking tested to IEC 60947-3)
SealingBy hand: screw ring or lidAutomatic once connected or lid shut (IP66/IP67/IP69 on most ranges)
Live-part protectionIP2X (finger)IP4X (1 mm wire), safety shutter
Impact resistanceIK06 to IK08IK09 to IK10
Pilot/auxiliary contacts1Up to 6

For the person at the machine this means a visible break right where they work, an emergency load-break, and a lock-off point for lockout/tagout, without walking back to the panel.

AC-22A, AC-23A and DC-21A in plain words

  • AC-21A: resistive loads such as heaters, with moderate overloads.
  • AC-22A: mixed resistive and inductive loads with moderate overloads, such as general machine supplies.
  • AC-23A: motors and other highly inductive loads, which draw a high current at start and are the hardest to switch.
  • DC-21A: resistive DC loads with moderate overloads. On the DSN and DS ranges this rating is given at 250 V DC.

Always read the rating for your category and your voltage. A DS9 is a 150 A connector, breaks 150 A in AC-22A up to 600 V, but 100 A of motor load at 440 V. Size by the motor current, not only the connector size.

DSN and DS ranges at a glance

The DSN ranges (DSN1, DSN3, DSN6) are compact, come in GRP or metal and are sealed to IP66/IP67/IP69. The DS ranges go higher in current and voltage, with GRP housings up to 150 A and metal housings from 90 to 250 A. All are rated for -40 °C to +60 °C ambient and a 10 kA short-circuit current.

RangeCurrentMax. voltageHousing and sealingMotor switching (AC-23A)Power
DSN116-20 A500 V AC / 750 V DCGRP or metal, IP66/IP67/IP6920 A at 500 V10 kW
DSN332 A690 V AC / 1000 V DCGRP or metal, IP66/IP67/IP6932 A at 480 V18.5 kW
DSN663 A1000 V AC / 1500 V DCGRP or metal, IP66/IP67/IP6963 A at 400 V30 kW
DS116-30 A690 V AC / 1000 V DCGRP, IP54 connected / IP55 lid shut30 A at 480 V15 kW
DS332-50 A1000 V AC / 1500 V DCGRP, IP54 connected / IP55 lid shut50 A at 400 V30 kW
DS663-90 A1000 V AC / 1500 V DCGRP or metal, IP66/IP6790 A at 400 V45 kW
DS9125-150 A1000 V AC / 1500 V DCGRP (also IP69) or metal, IP66/IP67100 A at 440 V80 kW
DS2200-250 A1000 V AC / 1500 V DCMetal, IP66/IP67160 A at 440 V-

Above 250 A, Marechal's high-current connectors (DS2 350 A, DS4 400 A and the single-pole DSP400 to DSP1250) do not break load; they carry pilot contacts that interlock with a switch or contactor. See the Marechal plugs and sockets page for all ranges.

Where DECONTACTORs are used

  • Motors and pumps: a socket next to the motor gives local disconnection and isolation for maintenance, and a motor can be swapped by unplugging it.
  • Mobile equipment and extension cables: a socket-outlet on a handle makes an in-line connector; finger draw plates help close in-line connections.
  • Food and pharmaceutical plants: IP69 versions stand up to high-pressure washdown up to +80 °C, and handles are offered with a silver-ion antibacterial additive.
  • Marine and offshore: the DSN series, DS9 and DS2 meet Bureau Veritas Marine specifications.
  • Variable-speed drives: metal versions with metal boxes, sleeves and shielded cable glands keep the screen continuous against electromagnetic interference.

Padlocking and lockout

An optional locking pin takes two padlocks with a 4 to 8 mm shackle (padlocks not supplied), so a socket can be locked with or without the plug in place. Other options include a larger release button, a self-closing lid and an IP66/IP67 cap for the inlet when it is unplugged.

What to send us for a quotation

The Marechal reference if you have it (it is laser-marked on the device). If not: the load and its kW or current, the supply voltage and frequency, the poles, GRP or metal, the mounting (wall box, sleeve angle or handle), the cable outer diameter and conductor size, any auxiliary contacts or padlocking, and the quantity. E-mail sales@sixwinds.com.sa or start from the Marechal plugs and sockets page.

Common questions

Can I pull a DECONTACTOR plug while the motor is running?

Yes, within the switching rating for motor loads (AC-23A) at your voltage. Press the release button: the switch inside the socket breaks the current and the plug comes out dead.

Will a standard CEE plug fit a DECONTACTOR socket?

No. The DECONTACTOR uses butt contacts, not pins and sleeves, and only mates with Marechal plugs and inlets of the same range and coding.

Do GRP and metal versions mate with each other?

Not on ranges that offer both: GRP devices are not compatible with metal devices, so order the plug and socket in the same material.

Do I still need a breaker for the circuit?

Yes. The DECONTACTOR replaces the local switch, not the circuit protection. The circuit still needs the breaker or fuses your design calls for.

Can a DECONTACTOR be locked off for maintenance?

Yes. With the locking pin option it takes two padlocks with a 4 to 8 mm shackle, which suits lockout/tagout procedures.

Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.

This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.