Appleton Ex e and Ex d junction boxes, enclosures and Unicode 2 control stations: how to choose

A junction box or control station in a hazardous area is chosen in a fixed order: the protection concept the area and the specification call for, the material that will survive the site, the terminals the cables need, and the entries and accessories that keep the certification intact. This guide follows that order through the Appleton enclosure and Unicode 2 ranges.

By the Six Winds engineering team · Updated

Quick answer

For terminals and cable joints in Zone 1, an increased safety box is the usual choice: aluminium JBEA/ECEA, 316L stainless JBES/ECES for corrosive locations, polycarbonate JBEL for small joints, or glass-fibre polyester JBEP for instrumentation and power. Where the equipment inside can spark, or the specification asks for Ex d, use a flameproof JBD, JBDR, AJBEW or a built-to-order JBDA/ECDA/ECDX. For push buttons, pilot lights and selectors, choose a Unicode 2 station in polyester (Ex e) or 316L stainless (Ex de).

Step by step

  1. Read the area dataTake the zone, the gas group and the temperature class from the area classification drawing, and check that the certificate of the box covers all three.
  2. Choose Ex e or Ex dTerminals and joints sit well in an increased safety (Ex e) box. Equipment that can spark in normal service, or a specification that names Ex d, needs a flameproof enclosure.
  3. Choose the material for the siteAluminium (JBEA, ECEA), 316L stainless steel for corrosive locations (JBES, ECES, Unicode 2 stainless), polycarbonate (JBEL) or glass-fibre reinforced polyester (JBEP, Unicode 2 polyester).
  4. Size the terminals for the cableJBEL takes 2.5/4 mm² (660 V) or 6/10 mm² (690 V) conductors; JBEP comes as instrumentation or power terminal boxes, or empty for your own layout.
  5. Plan the entries and glandsCount the cables, note armoured or unarmoured and the outer diameter, and pick M20 or M25 entries. Armoured cable needs an earth continuity path at the entry.
  6. For control stations, list the operatorsWrite down each push button, pilot light, selector, ammeter or emergency stop, its contacts (NO/NC) and its legend text, and the box size follows.
  7. Add the accessoriesDrain/breathers, earth studs, thread adaptors, spare inserts and keys, and padlockable guards are ordered as separate part numbers.

Ex e or Ex d: what changes for the box

An increased safety (Ex e) enclosure protects by construction: well-secured terminals, creepage and clearance distances, and a sealed housing so that no spark or hot spot arises in normal service. It is the usual home for terminals, cable joints and control devices that are themselves certified.

A flameproof (Ex d) enclosure is built so that an ignition inside cannot pass to the gas outside. It is chosen for equipment that can spark in normal service, or where the project specification names Ex d. Every entry on an Ex d box must keep that protection, so glands, plugs and adaptors must be certified for Ex d.

Some equipment combines the two: the Unicode 2 stainless stations, for example, are certified Ex de or Ex demb depending on the actuator fitted.

Increased safety boxes by material

RangeMaterialWhat it isAreas in our records
JBEAAluminiumPre-drilled junction boxZone 1
ECEAAluminiumEnclosure for terminals and equipmentZone 1
JBES316L stainless steelPre-drilled junction box for corrosive locationsZone 1
ECES316L stainless steelEnclosure for terminals and equipmentZone 1
JBELPolycarbonateSmall junction box supplied complete with terminalsZone 1, 2 (gas), 21, 22 (dust)
JBEPGlass-fibre reinforced polyesterTerminal box for instrumentation or power, or empty box undrilled or predrilledZone 1 (empty boxes: Zone 1, 2, 21, 22)

Aluminium suits general plant areas; 316L stainless is the choice for corrosive locations; polycarbonate JBEL is a light box for small joints; glass-fibre polyester JBEP gives large, non-metallic boxes for instrumentation and power marshalling.

JBEL: small polycarbonate boxes with terminals

Part numberCableVoltage · terminalsEntries supplied
JBEL1N4P16GUnarmoured, 2.5/4 mm²660 V · 28 A at 2.5 mm², 38 A at 4 mm²4 x PG16 with knock-out caps, 4 integrated glands for cable 8-16 mm
JBEL1A4M20Armoured, 2.5/4 mm²660 V · 28 A at 2.5 mm², 38 A at 4 mm²4 x M20 with brass earth continuity device, 2 blanking plugs
JBEL2N3M20G / JBEL2N4M20GUnarmoured, 6/10 mm²690 V · 42 A at 10 mm², 30 A at 6 mm², 18 A at 4 mm²3 or 4 x M20 with glands for cable 6.5-14.5 mm
JBEL2N3M25G / JBEL2N4M25GUnarmoured, 6/10 mm²690 V · as above3 or 4 x M25 with glands for cable 8-18.5 mm
JBEL2A4M20 / JBEL2A4M25Armoured, 6/10 mm²690 V · as above4 x M20 or 4 x M25 with brass earth continuity device, 2 blanking plugs
JBEL2A4M05 / JBEL2A4M06Armoured, 6/10 mm²690 V · as above2 x M25 + 2 x M20, or 3 x M25 + 1 x M20, with brass earth continuity device, 1 x M25 + 1 x M20 blanking plugs

Each JBEL has 4 terminals and 4 interconnected earth terminals (max. 1 x 4 mm² on the 2.5/4 mm² boxes, 1 x 10 mm² on the 6/10 mm² boxes). The N versions come with glands for unarmoured cable; the A versions have a brass earth continuity device for armoured cable, and you add the armoured glands. They weigh 0.4 kg (2.5/4 mm²) or 0.7 kg (6/10 mm²).

JBEP glass-fibre polyester boxes and gland plates

JBEP boxes come as instrumentation terminal boxes, power terminal boxes, or empty enclosures supplied undrilled or predrilled for drilling on site. Sizes (height x width x depth, mm) include 250 x 320 x 150, 500 x 320 x 150 and 230 deep, 750 x 320 x 150 and 230 deep, and the horizontal versions 320 x 500 and 320 x 750 in 150 or 230 deep.

Gland plates sit at the bottom, top and bottom, bottom and sides, or all sides depending on the size. Removable spare gland plates are available in plastic or brass, in size A (127 x 268 mm: JBEPGPPA plastic, JBEPGPBA brass) and size B (127 x 203 mm: JBEPGPPB plastic, JBEPGPBB brass), each with gasket and fixing hardware.

Flameproof (Ex d) boxes and built-to-order enclosures

  • JBD: pre-drilled flameproof terminal junction box, Zone 1.
  • JBDR: pre-drilled round flameproof junction box for conduit and cable junctions, Zone 1.
  • AJBEW: cast flameproof junction box, Zone 1.
  • JBDA, JBDF, ECDA, ECDF: flameproof enclosures built to order for terminals and electrical equipment, Zone 1.
  • ECDX: built-to-order flameproof enclosures in welded steel or stainless steel, Zone 1.

For a built-to-order enclosure send us the equipment to be housed, the cable entries (size, type and position), the temperature class and the ambient range, and we confirm the configuration with the certificate.

Unicode 2 control stations: polyester or 316L stainless

Polyester (U22, U23)316L stainless steel (U61, U62, U63)
BodyGlass-fibre reinforced polyester316L stainless steel body and cover, 304 stainless cover screws
ProtectionIncreased safety (Ex e)Ex de IIC or Ex demb IIC depending on the actuator; dust Ex tD A21
AreasZone 1, 2 (gas), 21, 22 (dust)Zone 1, 2 (gas), 21, 22 (dust)
Box sizesSize 2 (120 x 170 mm), size 3 (120 x 230 mm)Size 1, 2 and 3 (size 3: 220 x 187 mm, 89 mm deep)
Bottom entries2 x M20 (W2 in the number) or 2 x M25 (W4)2 x M20 (W2); 2 x M25 also listed on size 3 (W4)
Supplied withNameplate, brass earth continuity plate, blanking plug, cable glandNameplate, blanking plug, polyamide cable gland, 2 locknuts
Ratings in our recordsSee the certificate for each stationT5 to T6, IP66, IK10; contact blocks Ue 500 Vac / 110 Vdc, AC15 6 A/500 V; selector switches 690 V, max. 16 A

Ready-made stations cover the common duties: start/stop with or without pilot lights, three illuminated push buttons, emergency stop with push-pull or key release, mushroom-head push buttons, key push buttons, single pilot lights in red, green, blue, yellow or white, 2- and 3-position selectors, and a 48 x 48 mm ammeter combined with an I-0-II selector or with start/stop push buttons. The size 3 stainless station U63W2PGPRA5A9 weighs 2.1 kg and fixes with 2 x Ø8 mm holes.

Operators, inserts, legend plates and accessories

  • Contact blocks: UCB5R (1NO) and UCB9R (1NC). Up to 3 contacts per actuator; 2 at most on illuminated push buttons and key actuators.
  • Inserts: push button inserts (UIA…) and illuminated push button inserts (UIL…) in green, red, yellow, white, blue and black, unmarked or marked ON, OFF, START, STOP, I, O and more, in sets of 5.
  • Legend plates: yellow self-adhesive with black letters, small 40 x 19 mm (ULPS…) or large 50 x 25.3 mm (ULPL…), blank or with ready texts such as EMERGENCY STOP, HAND-OFF-AUTO, REMOTE-LOCAL, OPEN, CLOSE, RAISE and LOWER. Nameplates 58 x 18 mm (UNP…) in sets of 10.
  • Locking and guarding: padlockable guards UPLD1S (push buttons and rotary actuators) and UPLD2S (mushroom heads) take up to 3 padlocks of 6 mm shackle; yellow guard 098657 protects an emergency stop against accidental operation; spare key SK4A185 fits all key-operated actuators.
  • Cable glands (M20): 095605 polyamide, Ex e, for unarmoured cable 6.5-14.5 mm; 20E1FW5 (SWA) and 20E1FX5 (braid and tape) in nickel-plated brass, Ex e/Ex d, inner sheath 6.4-14.0 mm, outer 12.5-20.9 mm; all IP66.
  • Drain/breathers (M20, Ex e, IP66): DBE20P polyamide, DBE20B brass, DBE20S stainless steel, each with entry thread seal and locknut.
  • Earth and threads: PREESTM20 feed-through earth stud (M20 with M5 stud, 2.5 mm² green/yellow lead 300 mm); 20ETS2 nylon entry thread seal; 737DM2T15 and 737DM2T25 adaptors from M20 male to 1/2 in or 3/4 in NPT female (Ex d/Ex e).

Common questions

Which Appleton box suits a corrosive location?

The 316L stainless steel ranges: JBES junction boxes and ECES enclosures in increased safety, and the Unicode 2 stainless control stations. Built-to-order ECDX flameproof enclosures can also be made in stainless steel.

Can a JBEL box take armoured cable?

Yes. The A versions (for example JBEL2A4M20) have a brass earth continuity device at the entries for armoured cable; you add the armoured glands. The N versions are supplied with glands for unarmoured cable.

How many contact blocks can one Unicode 2 operator take?

Up to 3 contact blocks per actuator, and 2 at most on illuminated push buttons and key actuators. Contact blocks are UCB5R (1NO) and UCB9R (1NC).

Can the legend text be changed later?

Yes. Legend plates are self-adhesive and come in small and large sizes, blank or with ready texts; push button inserts can also be replaced, in sets of 5.

Can an emergency stop be locked off?

The UPLD2S padlockable guard fits mushroom-head actuators and takes up to 3 padlocks of 6 mm shackle (not supplied). The yellow guard 098657 protects the button against accidental operation.

Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.

This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.