Start from the current and whether the plug must be pulled under load (then it is a DSN or DS DECONTACTOR). Then fix the poles and voltage, GRP or metal, the IP and impact rating, and the cable size and outer diameter. Every socket-outlet and inlet needs a wall box, sleeve or handle, ordered as a separate item.
Step by step
- Fix the currentUse the full-load current of the equipment, then read the range from the table below. For motors, check the switching rating at your voltage, not only the connector size.
- Decide if it must break loadIf the plug will be pulled with the load running, choose a DECONTACTOR (DSN or DS, 16 to 250 A). Plain connectors and the high-current ranges must be connected off-load or interlocked.
- Set poles and voltage2P, 1P+N+E, 3P+E or 3P+N+E, the voltage and the frequency. Marechal codes each combination with a keying position so wrong plugs cannot enter.
- Choose GRP or metalGRP is light and does not corrode; metal adds impact strength and electromagnetic shielding. GRP and metal devices do not mate with each other.
- Check sealing and impactIP66/IP67 for wet and dusty areas, IP69 for hot high-pressure washdown, and IK09 or IK10 where the device can be hit.
- Match the cableCheck the conductor size against the terminal range, and the cable outer diameter against the gland on the handle or box.
- List the accessoriesWall box, inclined sleeve or handle for each device, plus caps, padlocking pins and cable glands as needed.
Current range to Marechal range
The table maps the current you need to the Marechal range that covers it. Where two ranges overlap, the DSN series is more compact and sealed to IP69, while the DS series goes to higher voltages (up to 1000 V AC).
| Current | Marechal range | Built-in switch (DECONTACTOR)? | Housing | Sealing |
|---|---|---|---|---|
| 16 A | PNC (4+E, also for 4-20 mA signals) | No | GRP | IP66/IP67/IP69 |
| 16-30 A | PN | No | GRP or metal | IP66/IP67 |
| 16-20 A | DSN1 | Yes | GRP or metal | IP66/IP67/IP69 |
| 16-30 A | DS1 | Yes | GRP | IP54/IP55 |
| 32 A | DSN3 | Yes | GRP or metal | IP66/IP67/IP69 |
| 32-50 A | DS3 | Yes | GRP | IP54/IP55 |
| 63 A | DSN6 | Yes | GRP or metal | IP66/IP67/IP69 |
| 63-90 A | DS6 | Yes | GRP or metal | IP66/IP67 |
| 125-150 A | DS9 | Yes | GRP or metal | IP66/IP67 (GRP also IP69) |
| 200-250 A | DS2 | Yes | Metal | IP66/IP67 |
| 400 A | DSP400 (single pole) | No | GRP or metal | IP66/IP67 |
| 500 A | CS1000 (single pole) | No | GRP | IP66/IP67 |
| 660 A | P66 (4P+E, up to 1.1 kV AC) | No | Metal | IP66/IP67 |
| 800 A | SP (single pole) | No | GRP | IP66/IP67 |
| 1250 A | DSP1250 (single pole) | No | Metal | IP66/IP67 |
Special ranges also exist for hot areas (PNHT up to 240 °C and DSHT 125 A up to 150 °C, both metal) and for multicontact control circuits (see below).
Switch-rated, plain connector or high-current
- DECONTACTOR (DSN and DS): a switch inside the socket breaks the load, so the plug can be pulled under load within its AC-22A, AC-23A or DC-21A rating.
- Plain connectors (PNC, PN): connect and disconnect off-load only.
- High current (DS2 350 A, DS4, DSP400, P66, SP, DSP1250): no breaking capacity; pilot contacts close last and open first, so a switch or contactor upstream drops the load before the contacts part. CS1000 has no pilot contact.
- Single-pole connectors (DSP400, CS1000, SP, DSP1250) are one per conductor, colour coded (L1 brown, L2 black, L3 grey, neutral blue, earth green, DC positive red, negative black) and mechanically keyed so phases cannot be mixed.
Poles, voltage and the reference number
Marechal offers up to 24 keying positions, each tied to a voltage and frequency, so only a plug and socket with the same coding can be joined. A 3P+N+E dual-voltage socket (230/400 V) can supply four plugs with the same coding: 3P+N+E and 3P+E at 400 V, 2P+E at 400 V, and 1P+N+E at 230 V.
Basic references have 7 characters: product line, housing, current, device type, a two-digit voltage code and the polarity. For example 6114017 reads DSN (6), blue GRP (1), 20 A (1), socket-outlet (4), 190-250/380-440 V (01), 3P+N+E (7). Replacing the second character with 5 gives a black GRP housing, and 9 is metal.
Housing, sealing and impact
GRP (glass-fibre reinforced polyester) is light and does not corrode. Metal housings reach IK10 and, combined with metal boxes, sleeves and shielded glands, keep the cable screen continuous for variable-speed drives. The P66 uses a copper-free aluminium alloy.
- IP66: powerful water jets. IP67: immersion for 30 minutes at 1 m. IP69: high-pressure cleaning at up to +80 °C. On Marechal devices the seal is made automatically when the plug is in or the lid is shut.
- IK08 / IK09 / IK10: impacts of 5, 10 and 20 joules.
- Most ranges are rated for -40 °C to +60 °C ambient.
Cable size and accessories
Terminal ranges (flexible / stranded) include: DSN1 1-2.5 / 1.5-4 mm², DSN3 and DS1 2.5-6 / 2.5-10 mm², DSN6 and DS3 6-16 / 10-25 mm², DS6 10-25 / 10-35 mm², DS9 25-70 / 25-95 mm², DS2 70-95 / 70-120 mm², DSP400 50-240 / 70-300 mm², CS1000 50-300 / 70-400 mm² and DSP1250 50-630 / 70-630 mm².
- Every socket-outlet and inlet needs a mounting accessory: a wall box, an inclined sleeve (for example 30° or 70°) or a handle. Handles are sold with or without a gland, by cable outer diameter.
- Cable glands are not supplied with the boxes; order them in the right thread and cable diameter.
- Options: inlet caps (IP66/IP67), self-closing lids, a locking pin for two padlocks (4-8 mm shackle), a larger release button and finger draw plates for in-line connections.
Multicontact connectors for control circuits
When power, control and signal wires must pass through one connector, for example on machines, test benches and moulds, Marechal multicontact ranges carry from 7 to 37 contacts: PN7C (6+E, 25 A), DN9C (8+E, 30 A), PN12C and DSN12C (11+E, 16 A), DN20C (19+E, 25 A), DSN24C (23+E, 16 A) and DSN37C (36+E, 16 A). PN12C, DSN12C, DSN24C and DSN37C use crimp contacts, and leaving two of their contacts unused gives 9 different keying positions.
What to send us for a quotation
The Marechal reference if you know it, read from the old device. If not: current, poles, voltage and frequency, GRP or metal, mounting (wall box, sleeve angle, handle or in-line), cable outer diameter and conductor size, whether it must break load, any auxiliary contacts or padlocking, and the quantity. E-mail sales@sixwinds.com.sa or browse the Marechal plugs and sockets page.
Common questions
Is a socket-outlet supplied with its wall box?
No. The socket-outlet or inlet is one item and the wall box, sleeve or handle is another, and boxes come without cable glands. List each part when you ask for a quotation.
Can I mix GRP and metal parts?
Not plugs and sockets: GRP devices do not mate with metal devices. Accessories must also match the range of the device.
Which range suits a 37 kW, 400 V motor?
Its full-load current is roughly 70 A, which is above the 63 A of DSN6, so look at DS6: it breaks 90 A of motor load at 400 V (45 kW). Send us the motor nameplate and we will confirm the range.
When do I need IP69?
Where equipment is cleaned with hot water at high pressure, as in food, dairy and pharmaceutical plants. The DSN ranges, PNC and GRP DS9 offer IP69.
Will a Marechal plug fit a CEE socket?
No. Marechal uses its own contact system and coding, so plugs and sockets must both be Marechal, of the same range and coding.