Up to 1 kV: ESTU terminations and ESIJ-OX joints for 4-core cable, ECKJ joints for armoured multi-core control cable and MCK kits for motor terminal boxes. From 7.2 to 36 kV: EPKT terminations, built from a code, and ESIJ or SXAW joints. Lugs and ferrules are not in the kits, so order them with the kit. Send us the print on the cable sheath and we will match the part numbers.
Step by step
- Read the cable sheathNote the rated voltage (often printed as Uo/U, sometimes with Um), the number of cores, the conductor size in mm², copper or aluminium, the insulation (XLPE/EPR or paper) and the armour or screen. A clear photo of the print is the quickest way to send it.
- Fix the voltage classThe kit must be rated for the class of the cable and system: up to 1 kV, 7.2, 12, 17.5, 24 or 36 kV. In the joint codes the figure before X tracks the class (OX, 2X, 3X, 4X, 6X); in EPKT codes it is 7, 17, 24 or 36.
- Match cores and conductor sizeEach kit covers a band of sizes, such as 50-95 mm². Your conductor size must fall inside the band, and the core count (1C, 3C or 4C) must match the cable.
- Match the armour or screenChoose /NA for no armour, /SA or /WA for wire armour and /TA for tape armour. Single-core cable with aluminium wire armour takes an SXAW joint. Add an ESPM earthing kit where the screen or armour must be bonded to earth.
- For terminations, choose indoor or outdoor and the tail lengthEPKT kits are coded I (indoor) or O (outdoor). Three-core terminations also need a tail length of 450, 650, 800 or 1200 mm; outdoor and 36 kV terminations have minimum tail lengths.
- Add what the kit does not includeLugs for terminations, ferrules for joints, and any boots, support insulators, cable box glands or earthing kits. Site teams also need a gas torch, such as the FH-1630 set, to shrink the components.
- Send us the detailsCable print or description, quantity of terminations or joints, indoor or outdoor, and the equipment the cable enters. We reply with the matching Raychem part numbers.
The facts that decide the kit
- Voltage class: the kits are graded up to 1 kV, 7.2 kV, 12 kV, 17.5 kV, 24 kV and 36 kV. A kit for a lower class must not be used on a higher-voltage cable.
- Number of cores: 4-core (most LV power cable), 3-core or single-core. Single-core MV kits are supplied per phase or per set of three, so check what one kit covers.
- Conductor size: in mm², matched to a size band. Lugs and ferrules are chosen to the same size and conductor material.
- Insulation: plastic (XLPE, EPR, EPDM, PVC) or mass-impregnated non-draining (MIND) paper. EPKT terminations are made for both; the ESIJ joints in our records are for plastic cable, and paper or mixed circuits use transition joints.
- Armour and screen: no armour, steel wire, steel tape or aluminium wire armour, and the metal screen of MV cable. This decides the joint suffix and the earthing kit.
- Location: indoor or outdoor for terminations; ESTU low-voltage terminations suit both.
Which family for which voltage
| Voltage class | Terminations | Joints | Other kits in the range |
|---|---|---|---|
| Up to 1 kV | ESTU-OX/4C: 4-core plastic cable, 4-16 mm² up to 500 mm² and over, not armoured or wire armoured (/WA) | ESIJ-OX/4C: 4-core, 1.5-300 mm², not armoured (/NA) or wire armoured (/SA) ECKJ: armoured multi-core control cable, 4-75 cores, 1.0-2.5 mm² | MCK motor kits (up to 1 kV); 302K, 402W and 502K breakouts; 102L end caps; MWTM and WCSM tubing |
| 7.2 kV | EPKT-7…: 1 or 3 cores, 16-1000 mm² | ESIJ-2X/1C 25-300 mm² (/NA) ESIJ-2X/3C 25-300 mm² (/NA, /SA) | MCK-5 motor kits (up to 7.2 kV) |
| 12 kV | EPKT-17…: 1 or 3 cores, 16-1000 mm² | ESIJ-3X/1C 16-300 mm² (/NA) ESIJ-3X/3C 16-300 mm² (/NA, /SA) | ESIB boots, ESPM earthing kits |
| 17.5 kV | EPKT-17…: 1 or 3 cores, 16-1000 mm² | ESIJ-4X/1C 25-630 mm² (/NA) ESIJ-4X/3C 25-300 mm² (/NA, /SA, /TA) SXAW-31x1: single-core, aluminium wire armour, 70-630 mm² | ESIN-4 support insulator (outdoor) |
| 24 kV | EPKT-24…: 1 or 3 cores, 25-1000 mm² | SXAW-51x1: single-core, aluminium wire armour, 120-630 mm² | ESPM earthing kits |
| 36 kV | EPKT-36…: 1 or 3 cores, 50-1000 mm² | ESIJ-6X/1C 35-630 mm² (/NA) ESIJ-6X/3C 35 mm² and over (/SA, /TA) SXAW-6132 and -6142: single-core, aluminium wire armour, 120-630 mm² | ESIN-6 support insulator, ESIB-6RL boots |
Transition joints, for cables of different sizes, plastic to paper cable, or one 3-core cable to three single-core cables, are made up to 36 kV and configured to the two cables being joined.
How the part numbers are built
Low-voltage and joint codes read from left to right. In ESTU-OX/4C 25-50/WA, ESTU is the low-voltage termination, OX the up-to-1 kV class, 4C four cores, 25-50 the conductor band in mm², and /WA wire armour (no suffix means not armoured). In ESIJ-4X/3C 50-95/SA, ESIJ is the straight joint, 4X the 17.5 kV class, 3C three cores, 50-95 the band and /SA wire armour; /NA is without armour and /TA tape armour.
EPKT medium-voltage terminations are built from a code: voltage (7, 17, 24 or 36), a size letter, cores (1 or 3), dielectric (X for polymeric XLPE/EPDM/EPR, M for MIND paper), location (I indoor, O outdoor), tail length for three-core cable (H1 450 mm, H2 650 mm, H3 800 mm, H4 1200 mm), then mod codes for accessories: B codes for boots and support insulators, G codes for earthing kits and glands, and E01 or E02 for a paper or plastic cable preparation kit.
Example: EPKT-17C3MOH3 B21 G43 is a 12/17.5 kV termination for 95-240 mm², three-core paper cable, outdoor, with an 800 mm tail, plus a B21 support insulator kit and a G43 armour earthing kit. The size letter depends on the voltage:
| Size letter | 7.2 kV (code 7) | 12 and 17.5 kV (code 17) | 24 kV (code 24) | 36 kV (code 36) |
|---|---|---|---|---|
| A | 16-50 mm² | 16-25 mm² | - | - |
| B | 70-120 mm² | 35-70 mm² | 25-50 mm² | - |
| C | 150-240 mm² | 95-240 mm² | 70-185 mm² | 50-95 mm² |
| D | 300-500 mm² | 300-400 mm² | 240-300 mm² | 120-185 mm² |
| E | 630-1000 mm² | 500-800 mm² | 400-630 mm² | 240-500 mm² |
| F | - | 1000 mm² | 800-1000 mm² | 630-1000 mm² |
Terminations: ESTU and EPKT
ESTU covers four-core plastic cable up to 1 kV, unarmoured or wire armoured, from 4-16 mm² up to 500 mm² and over, for indoor or outdoor use.
EPKT covers 7.2 kV to 36 kV, single- or three-core, from 16 mm² (25 or 50 mm² at the higher classes) up to 1000 mm². Single-core terminations have one tail length fixed by the voltage. For three-core cable the maker gives minimum tails: 650 mm for 17.5 kV outdoor and 36 kV indoor, and 800 mm for 24 kV outdoor and 36 kV outdoor.
Accessories for EPKT, ordered alone or by mod code:
- ESIB insulating boots (straight, right-angle long and short) let the termination work in compound- or oil-filled cable boxes with reduced air clearances. Supplied as a set of 3; ESIB-6RL goes up to 36 kV.
- ESIN support insulators carry outdoor terminations: ESIN-4 up to 17.5 kV and ESIN-6 up to 36 kV, each with a galvanised bracket.
- ESGL cable box glands for compound-filled boxes where the bushing-to-base-plate distance is short (25-95 and 120-300 mm², three-core).
- ESPM earthing kits, solderless, for metal tape screens and for wire, tape or corrugated armour, sized by core or under-armour diameter.
Joints: ESIJ, SXAW and transition joints
ESIJ straight joints run from 1 kV to 36 kV for plastic-insulated cable. The maker highlights quick installation, no shelf-life limit, high impact resistance and high earth-fault current capacity. Single-core kits hold material for one phase only, so a three-phase circuit needs three kits; ferrules are never included.
SXAW joints are for single-core screened polymeric cable with aluminium wire armour: SXAW-3121 to -3151 at 17.5 kV (70-630 mm²), SXAW-5131 to -5151 at 24 kV (120-630 mm²) and SXAW-6132 and -6142 at 36 kV (120-630 mm²).
Transition joints up to 36 kV link cables of different cross-sections, plastic to paper cable, or one three-core cable to three single-core cables. They are configured to the cables on each side, so send us both cable descriptions.
Control cable joints and motor connection kits
ECKJ joints are for armoured multi-core plastic control cable up to 1 kV with 1.0-2.5 mm² cores. Choose by core count: ECKJ-0017 for 4-7 cores, -0018 for 8-14, -0019 for 15-21, -0020 for 22-40 and -0021 for 41-75.
MCK motor connection kits replace tape and filler putty in a motor terminal box with heat-shrink caps. One kit covers a three-lead motor. The V type is a stub splice and the L type an in-line splice; MCK-1V to -4V and MCK-1L/-2L are for up to 1 kV, and MCK-5 versions for up to 7.2 kV. Pick by feeder cable size and lug length, for example MCK-3V for 25-95 mm² with an 82 mm lug.
For the cable ends and crutches around these kits the range also has 302K, 402W and 502K breakouts (2, 3 and 4 cores), 102L end caps and MWTM and WCSM adhesive-lined tubing up to 1 kV.
What comes in the kit and what to send us
| Kit | What is in the box | Order separately |
|---|---|---|
| EPKT single-core | Parts for 3 single-core terminations (one per phase) | Cable lugs; earthing kit, boots and insulators (or add their mod codes) |
| EPKT three-core | The termination with the tail length you chose (H1-H4) | Cable lugs; earthing kit, boots and insulators |
| ESIJ three- or four-core | Joint for one cable | Ferrules (connectors) |
| ESIJ single-core | Material for one phase only | Ferrules; two more kits for a three-phase circuit |
| ESIB boots | Set of 3 boots | - |
| ESIN insulator | Insulator with galvanised iron mounting bracket | - |
| ESGL gland | Straight cable box gland with mounting hardware | - |
| ESPM earthing kit | One piece, or material for all 3 cores, depending on the type | - |
| MCK motor kit | Insulating caps for one three-lead motor | - |
For a quotation send: the cable print or full description (voltage, cores, size, conductor material, insulation, armour), the number of terminations or joints, indoor or outdoor, the equipment or cable box the cable enters, and whether you need lugs, ferrules or earthing kits with the order. E-mail sales@sixwinds.com.sa.
Common questions
Are cable lugs included in an EPKT termination kit?
No. Lugs are ordered separately, sized to the conductor and its material. The same applies to ferrules in ESIJ joint kits.
Can an ESTU low-voltage termination be installed outdoors?
Yes. ESTU kits are made for indoor and outdoor use on four-core plastic cable up to 1 kV.
Which joint fits a 3-core, 17.5 kV, 95 mm² cable with steel wire armour?
ESIJ-4X/3C 50-95/SA: 4X is the 17.5 kV class, 3C three cores, 50-95 the size band and /SA wire armour. Add ferrules for 95 mm².
Do Raychem heat-shrink joints have a shelf life?
The maker states that the ESIJ joint system has no shelf-life limit. Store kits dry and out of direct sun all the same.
Can I terminate paper-insulated cable?
Yes. EPKT terminations come in an M version for mass-impregnated non-draining paper cable (not for draining paper cable). To join paper to plastic cable, use a transition joint.
Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.
This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.