Use OE outlet boxes, EL, ELFF and 8 series elbows and ECHF flexible couplings where an explosion-proof, dust-ignition-proof fitting is needed. Use Form 7 or Spec 5 conduit bodies for pulling and splicing in Class I, Division 2. Every conduit body needs a cover and a gasket of the same body size, or order a Spec 5 CG kit that packs all three. For the Ex e and Ex d boxes on the same job, add M20 drain/breathers and M20-to-NPT adaptors, and protect circuits with CBU breakers or CBD flameproof breaker enclosures.
Step by step
- Mark the classification along the runNote which parts of each conduit run are in Division 1, Division 2 or a safe area. The fitting at each point must be listed for that location.
- Choose the fitting by its jobPull, splice or change direction: an outlet box or conduit body. Bend: an elbow. Movement or vibration, such as a hanging light: a flexible coupling.
- Match the trade size and conduitOE boxes take threaded rigid metal conduit in 1/2 or 3/4 in; elbows are tapered NPT from 1/2 to 2 in; Form 7 and Spec 5 bodies run from 1/2 to 4 in for rigid conduit and IMC.
- Choose the finishStandard triple coat or zinc electroplate; -G for galvanizing on elbows and conduit bodies; SS for a stainless steel ECHF coupling.
- Order body, cover and gasket togetherEvery conduit body is ordered with a cover and a gasket of its body size, or as a Spec 5 CG kit with all three under one number.
- Add the parts for the Ex boxesDrain/breathers, M20-to-NPT thread adaptors, glands and earth studs for the metric Ex e and Ex d enclosures on the same system.
- Add the circuit protectionCBU breakers for fitting inside increased safety enclosures, or CBD flameproof enclosures with the breaker ordered separately.
Conduit in hazardous areas: Division 1 fittings and Division 2 bodies
A conduit installation keeps the wires inside threaded metal conduit from the source to the equipment. In a hazardous area, an explosion-proof fitting is built so that an ignition inside it cannot pass to the atmosphere outside, and a dust-ignition-proof fitting keeps dust out. The OE outlet boxes, EL, ELFF and 8 series elbows are listed explosion-proof and dust-ignition-proof for Class I Division 1 and 2 Groups C and D, Class II Division 1 and 2 Groups E, F and G, and Class III; the 1-1/2 and 2 in EL elbows also carry Class I Zone 1 and 2 Groups IIA and IIB.
Form 7 and Spec 5 conduit bodies are general-purpose bodies suitable for Class I Division 2 locations (NEC 501.10(B)(4)). They are not a substitute for an explosion-proof fitting in Division 1. Where the electrical code calls for conduit seals at a boundary or an enclosure, include them in your list; tell us the size and we quote them with the fittings.
OE outlet boxes
| Outlet box type | Hub arrangement | 1/2 in hubs | 3/4 in hubs |
|---|---|---|---|
| C | Straight through | 0EC-50 | 0EC-75 |
| LB | Back outlet | 0ELB-50 | 0ELB-75 |
| LL | Left outlet | 0ELL-50 | 0ELL-75 |
| LR | Right outlet | 0ELR-50 | 0ELR-75 |
| T | Tee | 0ET-50 | 0ET-75 |
OE boxes are compact explosion-proof outlet boxes in malleable iron with a triple-coat finish, supplied with a blank cover, for threaded rigid metal conduit. They are used to pull wires and change the direction of a run. They weigh between 0.68 kg (1/2 in C and LB) and 1.32 kg (3/4 in C).
Elbows and ECHF flexible couplings
- EL 90° elbows: EL-950 (1/2 in), EL-975 (3/4 in), EL-9100 (1 in), EL-9125 (1-1/4 in), EL-9150 (1-1/2 in) and EL-9200 (2 in), zinc electroplated, tapered NPT.
- 8 series: compact 90° elbows with one male and one female end: 8-50, 8-75 and 8-100 (1/2, 3/4 and 1 in).
- ELFF-450: short 45° elbow, 1/2 in.
- All three elbow types can be ordered with the -G suffix for a mechanically galvanized finish.
ECHF flexible couplings let a hanging pendant light fitting swing if it is struck, instead of breaking the conduit. They are brass tube with a bronze outer braid and an insulating liner, with bronze female ends and two removable steel close nipples, and provide a ground path. They are listed for Class I Division 1 and 2 Groups A, B, C and D, Class I Zone 1 and 2 Groups IIA, IIB and IIC, Class II Groups E, F and G, and Class III, and carry a maximum load of 50 lb. Sizes: 1/2 in (ECHF-50-4 to ECHF-50-18, flexible length 4, 6, 8, 10, 12, 15 or 18 in, minimum bending radius 254 mm) and 3/4 in (ECHF-75-4 to ECHF-75-12, 4 to 12 in, minimum bending radius 304.8 mm). Add SS for stainless steel.
Form 7 or Spec 5 conduit bodies
| Form 7 | Spec 5 | |
|---|---|---|
| Body material | Grayloy iron | Malleable iron, smooth bushed hubs, tapered NPT threads |
| Conduit | Rigid steel, rigid aluminium and IMC | Rigid conduit and IMC |
| Body types | C, E, L, LB, LL, TA | C, LB, LL, LR, T, TB, X |
| Trade sizes | 1/2 to 4 in (C to 3 in; LB and LL to 4 in; L and TA to 2 in; E to 1 in) | 1/2 to 4 in (TB and X to 2 in); built-in pulling rollers on types C and LB from 1-1/4 in |
| Finish | Triple coat (zinc electroplate, chromate, epoxy powder); -G hot dip galvanized | Triple coat; G versions hot dip galvanized (for example C-50G) |
| Covers | Wedge-Lok clip covers, stamped steel or cast iron; or covers with integral urethane gasket | BS domed-top steel or BC flat-top blank covers |
| Gaskets | Solid neoprene | SG Velbuna or SGN neoprene |
| Ready kit | – | CG: body + steel cover + neoprene gasket, types C, LB, LL, T, 1/2 to 2 in |
| Area | Class I, Division 2 | Class I, Division 2 |
Both families are used for pulling and splicing wires and changing the direction of a conduit run. The letters give the hub layout: C straight through, E dead end, L side outlet, LB back outlet, LL left, LR right, T tee, TA and TB tee with back outlet, X cross. Body capacity and maximum wire fill rise with size; for example a 4 in Spec 5 type C (C-400) takes 3 x 350 MCM.
Covers and gaskets: ordering a complete set
| Body size | Form 7 cover (stamped / cast) | Form 7 gasket | Spec 5 cover (domed / flat) | Spec 5 gasket (Velbuna / neoprene) |
|---|---|---|---|---|
| 1/2 in | 0ZG170 / 0ZG170F | 0ZGGASK571 | BS-50S / BC-50G | SG-50 / SGN-50 |
| 3/4 in | 0ZG270 / 0ZG270F | 0ZGGASK572 | BS-75S / BC-75G | SG-75 / SGN-75 |
| 1 in | 0ZG370 / 0ZG370F | 0ZGGASK573 | BS-100S / BC-100G | SG-100 / SGN-100 |
| 1-1/4 in | 0ZG470 / 0ZG470F | 0ZGGASK574 | BS-125S / BC-125G | SG-125 / SGN-125 |
| 1-1/2 in | 0ZG570 / 0ZG570F | 0ZGGASK575 | BS-125S / BC-125G | SG-125 / SGN-125 |
| 2 in | 0ZG670 / 0ZG670F | 0ZGGASK576 | BS-200S / BC-200G | SG-200 / SGN-200 |
| 2-1/2 and 3 in | 0ZG870 / 0ZG870F | 0ZGGASK578 | BS-250S / BC-250G | SG-250 / SGN-250 |
| 3-1/2 and 4 in | 0ZG970 / 0ZG970F | 0ZGGASK579 | BS-350S / BC-350G | SG-350 / SGN-350 |
A conduit body is not finished until it has a cover and a gasket of the same body size. Note that one Spec 5 cover or gasket fits two trade sizes in the larger bands (for example BS-125S fits 1-1/4 and 1-1/2 in bodies). Form 7 also offers covers with an integral form-in-place urethane gasket and captive screws, NEMA 3R, for -54 to +150 °C: 0ZG…IG (stamped steel), 0ZG…IGSA (stamped aluminium), 0ZG…FIG (cast iron) and 0ZG…FIGSA (cast aluminium); with these no separate gasket is needed.
Worked example: a 3/4 in Form 7 type LB: body 0ZGLB27, cover 0ZG270 (or 0ZG270F cast), gasket 0ZGGASK572; ask for the -G suffix if the body must be hot dip galvanized. The same job in Spec 5: LB-75CG, which packs the body, a steel cover and a neoprene gasket.
Drain/breathers, thread adaptors and glands on the Ex boxes
- Drain/breathers: DBE20P (polyamide), DBE20B (brass) and DBE20S (stainless steel), M20 male, Ex e, IP66, each with entry thread seal and locknut. Fit one at the lowest point of an enclosure so condensation can drain.
- Thread adaptors: 737DM2T15 (M20 male to 1/2 in NPT female) and 737DM2T25 (M20 male to 3/4 in NPT female), nickel-plated brass, Ex d/Ex e, IP66. They join metric Ex boxes to NPT conduit or fittings.
- Glands and earthing: M20 Ex e and Ex e/Ex d glands, the PREESTM20 earth stud and the 20ETS2 entry thread seal complete the entries. See the junction box guide for details.
CBU and CBD Ex circuit breakers
CBU miniature branch circuit breakers, tripping curve C, are made to be fitted inside increased safety enclosures in Zone 1 and 2 gas areas: 2-pole at 230/240 Vac and 3- or 4-pole at 380/415 Vac, each in 6, 10, 16, 20, 25 and 32 A (for example CBU216C, CBU332C, CBU416C). The 2-pole earth leakage (GFI) versions come in 10, 16 and 20 A with 30 mA (CBUN…CR1) or 300 mA (CBUN…CR2) sensitivity. Bracket 096650 mounts a 2-pole breaker through an enclosure door.
| Part number | Enclosure · protection | For | Max. current |
|---|---|---|---|
| CBDB0 / CBDC0 | CF2D · Ex d IIB T3 / CF1C · Ex d IIC T5 | 2-, 3- and 4-pole branch circuit breaker | 40 A / 25 A |
| CBDB6 / CBDC6 | CF2D · Ex d IIB T3 / CF1C · Ex d IIC T5 | 2-pole branch breaker with earth leakage (GFI) | 25 A / 25 A |
| CBDB7 / CBDC7 | CF2D · Ex d IIB T3 / CF1C · Ex d IIC T5 | 3-pole motor circuit breaker | 32 A / 32 A |
CBD flameproof enclosures house a breaker in Zone 1, 2, 21 and 22 gas and dust areas; the breaker itself is ordered separately. CF2D measures 240 x 145 x 212 mm and CF1C 185 x 170 x 175 mm; both weigh 4 kg. Ambient range: -25 to +55 °C for the branch breaker versions, -20 to +55 °C for the motor breaker versions, and -25 or -5 °C to +55 °C for the GFI versions depending on the breaker. For switching loads, RCU relays and contactors (2- or 4-pole, 20, 24, 40 or 63 A, up to 415 V) are made for increased safety enclosures in Zone 1 and 2.
Common questions
Can I use Form 7 or Spec 5 conduit bodies in Division 1?
No. In our records Form 7 and Spec 5 bodies are listed for Class I, Division 2. In Division 1 use explosion-proof fittings such as the OE outlet boxes and EL elbows.
Does a conduit body come with its cover and gasket?
Not as a rule: the body, cover and gasket are separate part numbers of the same body size. The Spec 5 CG kits (for example LB-75CG) pack all three, and Form 7 covers with an integral gasket replace the cover and gasket in one part.
What is an ECHF flexible coupling used for?
It joins a hanging pendant light fitting to the conduit so the fitting can swing if struck. It is explosion-proof and dust-ignition-proof, provides a ground path and carries up to 50 lb.
What does the -G suffix mean?
On Form 7 and Spec 5 conduit bodies it means hot dip galvanized; on EL, ELFF and 8 series elbows it means mechanically galvanized. The standard finish is triple coat on bodies and zinc electroplate on elbows.
Is the breaker included in a CBD enclosure?
No. The CBD flameproof enclosure is supplied empty for the breaker type it is certified for, and the breaker is ordered separately. Tell us the breaker type and rating and we quote both.
Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.
This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.