The Champ VMVL is a Zone 2 gas (Ex ec mb IIC Gc) and Zone 21 dust (Ex tb IIIC Db) luminaire, and Class I Division 2 under NEC/CEC. It is not for Zone 1. With the UNV1 driver the VMVL-3 to VMVL-11 is T5 up to 55 °C ambient and T4 up to 65 °C (with exceptions in the table). It is IP66 and Type 4X, has 6 kV surge protection and works from -40 to 65 °C ambient.
Step by step
- Get the area classificationTake the zone, gas group, temperature class and any dust zone for each lighting point from the hazardous area classification drawing and schedule.
- Confirm the zoneZone 2 gas and Zone 21 or 22 dust (or Class I Division 2) are within the VMVL rating. Zone 1 and Zone 0 are not.
- Check the gas groupThe VMVL is IIC, the most demanding gas group, so it also covers IIA and IIB areas.
- Match the temperature class to the ambientRead the column for your design ambient temperature (40, 55 or 65 °C) for your model and driver, and check the class is at least as strict as the area needs.
- Check the driverThe ATEX and IECEx markings are given for the UNV1 luminaire (100-277 VAC, 127-250 VDC). For an IECEx or ATEX project choose UNV1.
- File the certificatesKeep the certificate numbers, the marking and the special conditions of use in the Ex register, and install to your Ex installation standard.
Reading the ATEX and IECEx marking
The UNV1 luminaire carries these markings, with the certificates IECEx UL 13.0052X, DEMKO 13 ATEX 1305741X and DEMKO 13 ATEX 1475031X:
- II 3 G Ex ec mb IIC T5 Gc, -40 °C to +40 °C
- II 3 G Ex ec mb IIC T5 Gc, -40 °C to +55 °C
- II 3 G Ex ec mb IIC T4 Gc, -40 °C to +65 °C
- II 2 D Ex tb IIIC T72 °C Db, -40 °C to +40 °C
- II 2 D Ex tb IIIC T87 °C Db, -40 °C to +55 °C
- II 2 D Ex tb IIIC T92 °C Db, -40 °C to +65 °C
| Part of the marking | What it means |
|---|---|
| II 3 G | Equipment group II (surface industry), category 3, gas: suitable for Zone 2 |
| Ex ec | Increased safety, protection level "ec" |
| mb | Encapsulation, protection level "mb", used for parts inside the luminaire |
| IIC | Gas group IIC, which also covers IIB and IIA gases |
| T5 / T4 | Temperature class: highest surface temperature 100 °C (T5) or 135 °C (T4), depending on ambient |
| Gc | Equipment protection level for gas Zone 2 |
| II 2 D | Equipment group II, category 2, dust: suitable for Zone 21 (and Zone 22) |
| Ex tb | Protection by enclosure, level "tb" |
| IIIC | Dust group IIIC (conductive dust), which also covers IIIB and IIIA |
| T72 °C / T87 °C / T92 °C | Highest surface temperature for dust at 40, 55 and 65 °C ambient |
| Db | Equipment protection level for dust Zone 21 |
The X at the end of each certificate number means the certificate sets specific conditions of use. Read them before installation and keep them with the Ex register. The IEC and ATEX certification applies to the 100-277 VAC and 127-250 VDC voltage range. The standards behind it are IEC/EN 60079-0, 60079-7, 60079-18 and 60079-31, with IEC/EN 60529 for ingress protection and IEC/EN 60598-1 and 60598-2 for luminaires.
North American ratings: Division 2 and Zone 2 AEx
For plants designed to NEC or CEC rules the VMVL is listed for Class I Division 2 Groups A, B, C and D; Class II Groups E, F and G; Class III; Class I Zone 2 AEx ec mb IIC; Zone 21 tb IIIC; simultaneous presence of gas and dust; and wet locations, Type 4X, IP66. It is tested to UL 844 (luminaires for hazardous locations), UL 1598 and UL 1598A (marine), and CSA C22.2 No. 137. Vibration was tested to Section 33 and impact to Section 68 of UL 844.
A Saudi plant may be classified in Zones (IEC) or in Divisions (NEC), depending on its design basis, and some packaged units arrive with the other system. The VMVL carries both, so check which system your drawing uses and read the matching row.
Temperature class against ambient temperature
| UNV1 model | Rating | 40 °C | 55 °C | 65 °C |
|---|---|---|---|---|
| VMVL-3 to VMVL-11 | Class I Zone 2, AEx ec mb / Ex ec mb | T5 | T5 (T4 for VMVL-11 with R1 or R3) | T4 |
| Class I Division 2 | T5 | T5 | T4A | |
| Zone 21 AEx tb IIIC, Class II/III | T72 | T72 | T92 | |
| VMVL-7, 9 and 11 with S892 | Class I Zone 2 | T4 | T4 | T4 |
| Class I Division 2 | T5 | T4A | T4A | |
| Zone 21 AEx tb IIIC, Class II/III | T72 | T87 | T92 | |
| VMVL-13 | Class I Zone 2 | T5 | T4 | not listed |
| Class I Division 2 | T4A | T4A | not listed | |
| Zone 21 AEx tb IIIC, Class II/III | T64 | T77 | not listed | |
| VMVL-13 with S892 | Class I Zone 2 | T4 | T4 | not listed |
| Class I Division 2 | T5 | T4A | not listed | |
| Zone 21 AEx tb IIIC, Class II/III | T64 | T77 | not listed |
The temperature class must be at least as strict as the area requires: a T4 fitting can go into a T3 area but not a T5 area. Use the design ambient in your project specification. In the Kingdom it is often well above 40 °C, so read the 55 °C or 65 °C column, not the 40 °C one. The brochure gives VMVL-13 codes up to 55 °C only. For dust, the maker's ATEX/IECEx marking gives T72 °C, T87 °C and T92 °C at 40, 55 and 65 °C; always go by the nameplate of the luminaire supplied.
The UNV34 tables list Class I Division 2 (T5, T5, T4A for VMVL-3 to -11; T4A at 40 and 55 °C for VMVL-13), Class II Division 1 and simultaneous ratings, but no Zone 2 row, and the ATEX/IECEx markings are given for UNV1 only.
Why the VMVL is not a Zone 1 fitting
Category 3 G and protection level Gc mean the luminaire is made for areas where a gas atmosphere is unlikely in normal operation and, if it occurs, lasts only a short time: Zone 2. Zone 1, where a gas atmosphere is likely in normal operation, needs equipment with protection level Gb or Ga (category 2 G or 1 G). In the same way, the Class I rating is Division 2, not Division 1.
So when an HID fitting is replaced, check the zone of each point. Any point inside Zone 1, for example close to pump seals, compressors or loading arms where the drawing shows Zone 1, needs a Zone 1 luminaire; ask us and we offer a fitting certified for that zone.
Enclosure, surge and climate ratings
- IP66 and Type 4X: dust-tight and protected against powerful water jets, for wash-down and outdoor process areas.
- Surge: 6 kV IEC rated as standard (6 kV/3 kA line to line, 10 kV/0.83 kA line to ground); the SG1 option adds an ANSI rating (6 kV/3 kA line to line and line to ground).
- Ambient: -40 °C to 65 °C operating range, and up to 60,000 hours life at 55 °C.
- Materials: die-cast aluminium housing with Corro-free epoxy powder coat, silicone gaskets and stainless steel external hardware; the luminaire is factory sealed and needs no external seals.
- Heat fins: shaped for air flow and to shed dust, which helps on sandy, hot sites.
Dust areas: Zone 21 and Zone 22
With the Ex tb IIIC Db marking the VMVL may be used where combustible dust is present, such as powder and pellet handling, bagging and storage. IIIC covers conductive dust, the most demanding group. Compare the maximum surface temperature (T72 °C to T92 °C, depending on ambient and model) with the limit the site sets from the dust's ignition temperatures. The listing for simultaneous presence covers areas where gas and dust may both be present.
Documents to keep and what to send us
For the Ex register keep the certificate numbers, a photo of the nameplate, the model and driver, and the special conditions of use. For a quotation send the zone, gas group, temperature class and design ambient for each area, the quantity and size, the mounting and the supply voltage. The Champ VMVL range page lists the models and the catalogue number builder helps you write the part number, or e-mail sales@sixwinds.com.sa.
Common questions
Can the Champ VMVL be installed in Zone 1?
No. It is certified for Zone 2 gas (category 3 G, Gc), Zone 21 dust and Class I Division 2. A Zone 1 point needs a luminaire certified for Zone 1.
Is the VMVL suitable for hydrogen areas?
Its gas group is IIC, which includes hydrogen, and IIC also covers IIA and IIB gases. The zone must still be Zone 2 and the temperature class must suit the area.
What temperature class does the VMVL have at 55 °C?
In Zone 2 with UNV1: T5 for VMVL-3 to VMVL-11 (T4 for VMVL-11 with R1 or R3 optics), T4 for VMVL-13 and for the S892 redundant-driver versions.
Does the UNV34 version carry ATEX and IECEx markings?
The brochure gives the ATEX and IECEx markings for the UNV1 luminaire only. The UNV34 tables list North American Division ratings. For an IECEx or ATEX project choose UNV1.
What do IP66 and Type 4X mean?
IP66 means dust-tight and protected against powerful water jets. Type 4X is the North American enclosure rating for indoor and outdoor use with protection against hose-directed water and corrosion.
Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.
This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.