Choosing Appleton explosion-proof plugs and receptacles: Ex e, Ex d or U-Line for Class and Division

Appleton plugs and receptacles for hazardous areas fall into three families: increased safety (Ex e) ranges for plants classified in zones, a flameproof (Ex d) range that reaches 125 A, and U-Line receptacles listed for the North American Class and Division system. The right choice starts with how your plant classifies the area, then the current, the poles and how the outlet is mounted.

By the Six Winds engineering team · Updated

Quick answer

If the plant is classified in zones, choose an Ex e range (UPR, PRE or MRE, up to 125 A with PRE) or the flameproof PRD range in 16, 32, 80 or 125 A. If the plant follows Class and Division, choose U-Line EFS receptacles with the ECP plug, rated 20 A at 125 Vac or 250 Vac. Then fix the poles, the socket style or conduit hub, and order the earthing and cover accessories together with the outlets.

Step by step

  1. Confirm how the area is classifiedZone 1, 2, 21 or 22 on the area classification drawing points to the IEC ranges (UPR, PRE, MRE, PRD). Class I, II or III with Division 1 or 2 points to U-Line. Take the gas or dust group and the temperature class from the drawing, not from habit.
  2. Choose the protection typeIncreased safety (Ex e) covers most general power outlets from 16 to 125 A. Flameproof (Ex d) PRD is the choice where the specification asks for Ex d, and it is the only one of these ranges with an 80 A rating.
  3. Set the current16 and 32 A: UPR, PRE, MRE or PRD. 63 A: PRE. 80 A: PRD. 125 A: PRE or PRD. U-Line receptacles and the ECP plug are 20 A.
  4. Fix the poles and the voltagePRE 16 A comes as 2P, 2P+E, 3P, 3P+E and 3P+N+E; PRE 32 A as 2P+E, 3P+E and 3P+N+E. U-Line is 2-wire, 3-pole, either 125 Vac 1 HP or 250 Vac 2 HP.
  5. Choose the socket style or the conduit hubPRE sockets are offered wall-mounting, mobile or flush. U-Line receptacles are single-gang or two-gang, dead-end or feed-thru, with a 1/2, 3/4 or 1 in conduit hub.
  6. Add plugs, accessories and sparesCount one plug per piece of portable equipment, then add the PRE earthing accessories, U-Line spare covers, spring-loaded cover assemblies or the NEMA 4X screw cover kit as the site needs.

Three families: Ex e, Ex d and Class/Division

Increased safety (Ex e) plugs and sockets are built so that sparks and hot surfaces do not arise in normal service. In the Appleton range this covers UPR (plug and switched socket, 16 and 32 A), PRE (plug and socket, 16 to 125 A, for Zone 1, 2, 21 and 22) and MRE (multiple socket outlet assemblies with 16 or 32 A sockets).

Flameproof (Ex d) equipment is built so that an ignition inside the housing cannot spread to the gas around it. The PRD range is a flameproof plug and socket in 16, 32, 80 and 125 A, intended for heavy-duty power outlets.

U-Line receptacles follow the North American system of Classes, Divisions and Groups. They are 20 A factory-sealed receptacles with a dead-front design, used with the matching ECP plug. Plants designed to that system, or skids built for it, specify them by Class, Division and Group rather than by zone.

Which series for which current and protection

CurrentIncreased safety (Ex e), zonesFlameproof (Ex d), zonesClass / Division (NEC)
16 AUPR (switched socket) · PRE · MRE (multiple outlet)PRD–
20 A––U-Line EFS receptacle + ECP plug, 125 Vac 1 HP or 250 Vac 2 HP
32 AUPR (switched socket) · PRE · MRE (multiple outlet)PRD–
63 APRE––
80 A–PRD–
125 APREPRD–

Two questions settle most selections: does the area use zones or Class/Division, and what current does the equipment draw? Where a rating appears in more than one column, the project specification decides between Ex e and Ex d.

Increased safety ranges: UPR, PRE and MRE

  • UPR: plug and switched socket outlet in 16 and 32 A, for powering portable equipment in hazardous areas. The switch lets the socket be made dead before the plug is withdrawn.
  • PRE: plug and socket in 16, 32, 63 and 125 A for gas and dust zones (Zone 1, 2, 21, 22). The 16 and 32 A sizes are offered as wall-mounting, mobile and flush sockets with matching plugs.
  • MRE: multiple socket outlet assemblies with 16 A or 32 A sockets, useful where several portable loads are fed from one point.

Useful PRE dimensions for planning panel and wall space: the 16 A plug is 152 mm long (2P, 2P+E, 3P), 154 mm (3P+E) or 166 mm (3P+N+E); the 32 A plug is 170 mm (2P+E, 3P+E) or 195 mm (3P+N+E), and the 32 A wall socket stands 370 mm (2P+E, 3P+E) or 375 mm (3P+N+E) high.

Flameproof PRD for heavier loads

PRD plugs and sockets are flameproof (Ex d) and come in 16, 32, 80 and 125 A. Choose PRD where the project calls for Ex d outlets, or where an 80 A outlet is needed, since none of the Ex e ranges above has an 80 A size. Give us the current, the number of poles and the voltage, and we confirm the exact catalogue number with the certificate.

U-Line EFS receptacles for Class and Division plants

In the part numberMeaningExample
EFS / EFSCDead-end / feed-thru receptacleEFS150-2023 / EFSC150-2023
1 or 2 after the lettersSingle-gang / two-gangEFS150-2023 / EFS250-2023
50 · 75 · 10Conduit hub 1/2 in · 3/4 in · 1 inEFS175-2023 (3/4 in hub)
-2023 / -20232125 Vac, 20 A, 1 HP / 250 Vac, 20 A, 2 HPEFS150-20232
M at the endMalleable iron cover and box (without M: aluminium cover, malleable iron box)EFS150-2023M
B after EFS or EFSCSeparate factory-sealed chamber, Class I Groups B, C, D without external seals (single-gang, 1/2 or 3/4 in hub)EFSB150-2023M, EFSCB175-20232M
  • Area ratings: standard single-gang receptacles are listed for Class I Division 1 and 2 Groups C and D, and Group B with external seals; Class II Division 1 and 2 Groups F and G; and Class III. Two-gang receptacles are listed for Class I Division 1 and 2 Groups C and D, and Class I Division 2 Groups B, C and D. The B versions (EFSB, EFSCB) carry Class I Groups B, C and D with no external seals.
  • Enclosure types: NEMA 3, 3R, 3RX, 4X, 7BCD and 9FG.
  • Materials: aluminium cover on a malleable iron box, or malleable iron cover and box (M suffix).
  • ECP plug: 20 A, copper-free aluminium housing (0.4% copper max.), glass-fibre reinforced polyester insulating blocks, for cord of .538 to .639 in diameter. It fits U-Line receptacles and standard NEMA 5-20R and 6-20R receptacles.

Switching, interlock and covers

  • Switched sockets: UPR combines the socket with a switch, so the outlet is switched off before the plug is connected or removed.
  • U-Line twist action: the ECP plug is pushed in and twisted; the twist locks it in and operates the receptacle switch, and the receptacle itself is factory sealed with a dead-front design.
  • Covers: a spring-loaded cover (spare assembly ULSCA) closes the U-Line receptacle when no plug is in it. For corrosive or wash-down areas, the ULINEREC4XKIT screw cover kit gives NEMA 4X when the screw cover is fully engaged.
  • Spare receptacle covers: EFSR-2023 (125 Vac, 1 HP) and EFSR-20232 (250 Vac, 2 HP) in aluminium, and EFSR-2023K / EFSR-20232K for SWB mounting boxes.

Accessories and what to send us for a quotation

For PRE 32 A outlets, two earthing accessories keep the earth path continuous through the entry: PREECAM25, an M25 earth continuity adaptor, and PREESTM25, an M6 earth stud. Both come with a black neoprene sealing washer and a 300 mm green/yellow earth conductor, and are rated Ex e, IP66.

For a quotation send: the area classification (zone, or Class/Division and Group), the series if you know it, the current, the poles (for example 3P+E), the voltage, the socket style or conduit hub size, the number of plugs, and any covers or earthing accessories. Search the Appleton part numbers or e-mail sales@sixwinds.com.sa.

Common questions

What is the difference between Ex e and Ex d plugs and sockets?

Ex e (increased safety) equipment is built so that sparks and hot surfaces do not arise in normal service; Ex d (flameproof) equipment is built so that an ignition inside cannot spread outside. UPR, PRE and MRE are Ex e; PRD is Ex d. The area classification and the project specification decide which is required.

Which Appleton series covers 63 A, 80 A or 125 A?

PRE covers 63 A and 125 A in increased safety. PRD covers 80 A and 125 A in flameproof construction, as well as 16 and 32 A.

Will the U-Line ECP plug fit a standard 20 A receptacle?

Yes. The ECP plug mates with U-Line explosion-proof receptacles and with standard NEMA 5-20R and 6-20R receptacles.

Do U-Line receptacles need external conduit seals?

For Class I Group B, standard single-gang receptacles are listed with external seals. The EFSB and EFSCB versions have a separate factory-sealed chamber and need no external seals. Follow the electrical code and the site rules for every other case.

Can I order spare covers for U-Line receptacles?

Yes: EFSR-2023 and EFSR-20232 replacement covers, EFSR-2023K and EFSR-20232K for SWB mounting boxes, the ULSCA spring-loaded cover assembly and the ULINEREC4XKIT NEMA 4X screw cover kit.

Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.

This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.