On a high-voltage cable the accessories are engineered to the cable, the equipment and the site, so the choice starts from a short list of numbers: the highest system voltage Um, the impulse level, the conductor size, the diameter over the prepared insulation and, outdoors, the pollution level. This guide sets out the Raychem families from 52 kV to 245 kV and the figures that separate them.

By the Six Winds engineering team · Updated

Quick answer

Find Um and the BIL your specification asks for, then pick by where the cable ends: open air (OHVT heat-shrink, composite, porcelain or dry), indoors (IHVT), gas-insulated switchgear (PHVS) or a transformer (PHVT). Choose the outdoor creepage for the site pollution, the joint type and its outer protection, and plan the sheath bonding and link boxes with the cable route. Every HV kit is confirmed against the cable drawing before order.

Step by step

  1. Fix Um and the impulse levelTake the highest system voltage Um and the required lightning impulse (BIL) from the specification. The Raychem classes run 52, 72.5, 123, 145, 170 and 245 kV.
  2. Collect the cable dataConductor size and material, insulation diameter over the prepared insulation, maximum diameter over the outer sheath, metallic sheath or screen design, and any built-in optical fibres. The cable maker's drawing has all of these.
  3. Decide where each cable end goesOpen-air outdoor structure, indoor room, gas-insulated switchgear or transformer. This decides between OHVT, IHVT, PHVS and PHVT.
  4. Choose the outdoor creepageFor outdoor terminations, match the creepage distance to the site pollution level. Coastal, desert-dust and industrial sites often call for the longer variants.
  5. Choose the jointsHeat-shrink EHVS-H at 52-72.5 kV, one-piece EHVS-S or three-piece EHVS-T above that; then the outer protection (W, C, B or H) and the screen treatment (inline, shield break or grounded) that the bonding design needs.
  6. Plan connectors and sheath bondingPick the top connector for the busbar or line, then the link boxes for the bonding scheme: single-point earthing or cross-bonding, buried or above ground, with or without sheath voltage limiters.
  7. Send us the packageCable drawing, Um and BIL, number of terminations and joints of each type, switchgear or transformer interface, site pollution class and the bonding single-line diagram. We return the matching Raychem selection for your engineer to confirm.

Um, rated voltage and BIL

HV accessories are rated by Um, the highest voltage of the system they serve, with the cable's rated voltage U and the lightning impulse withstand (BIL) alongside. IEC 60840 covers the classes up to 170 kV in our records and IEC 62067 the 245 kV class; IEC 60815 is cited for outdoor creepage.

UmRated voltage ULightning impulse (BIL)Test standardTerminations in our recordsJoints
52 kV45-47 kV250 kVIEC 60840IHVT-52H, OHVT-52HEHVS-52H
72.5 kV60-69 kV325 kVIEC 60840IHVT/OHVT/LHVT-72H, OHVT-72C, OHVT-72P, PHVS-72, PHVT-72EHVS-72H
123 kV110-115 kV550 kV (OHVT-123P); 325 kV reduced level for OHVT-123HIEC 60840OHVT-123H, OHVT-123P-
145 kV132-138 kV650 kVIEC 60840OHVT-145C, OHVT-145P, OHVT-145D, PHVS-145, PHVT-145EHVS-145S, EHVS-145T
170 kV150-161 kV750 kVIEC 60840OHVT-170C, PHVS-170, PHVT-170EHVS-170T
245 kV220-230 kV1050 kVIEC 62067OHVT-245C, OHVT-245P, PHVS-245, PHVT-245EHVS-245S

Terminations at a glance

FamilyWhere it goesHow it is builtUm in our recordsConductor
IHVT-HIndoorHeat-shrink stress control tube with non-tracking outer tube and sheds; no oil or compound52, 72.5 kV95-2500 mm²
OHVT-H / LHVT-HOutdoor; LHVT with extended creepageAs IHVT-H, longer and with greater creepage52, 72.5, 123 kV95-2500 mm² (123 kV: 95-1600; LHVT: 300-2500)
OHVT-COutdoor, including heavily polluted sitesLight, pressure-tight composite housing, factory-tested silicone-rubber stress cone, silicone-oil filled without preheating72.5, 145, 170, 245 kV95-2500 mm² (245 kV: 300-2500)
OHVT-POutdoorPorcelain housing, silicone-rubber stress cone, silicone-oil filled72.5, 123, 145, 245 kV95-1200 mm² (245 kV: 300-2500)
OHVT-DOutdoor, self-supportingDry: plug-in part with stress cone in an epoxy insulator with moulded silicone sheds; no oil or gel; short cable cut-back145 kV95-1200 mm²
PHVSGas-insulated switchgear (GIS)Dry plug-in into an epoxy insulator; interface to IEC 62271-209; works in SF6 or insulating liquid72.5, 145, 170, 245 kV95-2500 mm² by class
PHVTTransformers and other equipmentDry, separable plug-in with corona shield; SF6 or insulating liquid such as transformer oil72.5, 145, 170, 245 kV95-2500 mm² by class

Heat-shrink terminations are modular and need no filling. Composite and porcelain units carry a factory-tested silicone-rubber stress cone and are filled with silicone oil. The dry OHVT-D has no oil or gel, and its plug-in part can be fitted to the cable in the workshop beforehand.

Outdoor terminations: creepage and pollution

Creepage, the distance along the insulator surface, is what keeps an outdoor termination clean of flashover in dust, salt and industrial pollution. Composite OHVT-C housings come in several creepage lengths per class, up to 50 mm/kV, for common and extreme pollution levels.

UmOHVT-C composite (minimum creepage)OHVT-P porcelainHeat-shrink and dry-type
52 kV--IHVT-52H approx. 1100 mm; OHVT-52H approx. 1540 mm
72.5 kV-2A 2164 mm; -2B 2383 mm; -2C 3089 mm-72P-2A 2350 mmIHVT-72H approx. 1600 mm; OHVT-72H approx. 2300 mm; LHVT-72H approx. 3100 mm
123 kV--123P-4B 3910 mmOHVT-123H approx. 3100 mm
145 kV-2A 3392; -3A 3829; -4A 4684; -4B 6100; -4C 8047 mm-145P-4A 4300 mmOHVT-145D 4680 mm
170 kV-1A 3829; -3A 4273; -4A 5373; -4B 5746; -4C 9436 mm--
245 kV-2A 5161; -3A 5605; -4A 6160; -4B 8401; -4C 10171 mm-245P-4A 9100 mm-

Optional add-ons for outdoor terminations: arcing horns with an adjustable gap that keep flashovers off the insulator surface; a lifting device (terminations up to 170 kV, sheath up to 110 mm, up to 500 kg) so the termination can be built and filled on the ground and raised with its cable; an oil drain flange for drawing oil samples later; and a fibre-optic add-on kit for two steel pipes of up to 24 fibres each.

Plug-in terminations for switchgear and transformers

PHVS terminates the cable inside gas-insulated switchgear and PHVT inside transformers and similar equipment. Both are dry, with no oil filling on site: a plug-in part with a silicone-rubber stress cone goes into a pressure-tight epoxy insulator that the equipment maker can fit in advance. They work in SF6 or in an insulating liquid.

SizeBILConductorInsulation diameter (prepared)Max. sheath diameterMin. creepage
PHVS-72 / PHVT-72325 kV95-2000 mm²34-78 mm120 mm255 mm
PHVS-145 / PHVT-145650 kV95-2500 mm²34-78 mm up to 1200 mm²; 73-108 mm from 1200 mm²120 / 135 mm414 mm
PHVS-170 / PHVT-170750 kV1000-2500 mm²73-108 mm135 mm414 mm
PHVS-245 / PHVT-2451050 kV300-2500 mm²77-119 mm150 mm519 mm

Related parts: a re-usable blind plug closes the socket so the equipment can run at nominal voltage before the cable arrives, and a pressure-tested test plate lets the insulator be pressurised with SF6 during switchgear testing.

Joints: EHVS-H, EHVS-S and EHVS-T

JointDesignUmConductorInsulation diameter (prepared)Length
EHVS-52H, -72HModular heat-shrink tubes over a torque-controlled connector; no special tools52, 72.5 kV95-2500 mm²30-86 mm1350 mm
EHVS-145SOne-piece pre-moulded silicone rubber body, factory tested145 kV500-2500 mm²60-112 mm2400-3000 mm
EHVS-245SOne-piece pre-moulded silicone rubber body, factory tested245 kV300-2500 mm²71-119 mm2500-3500 mm
EHVS-145TThree-piece: main body plus two adapters; short cut-back, size transition possible145 kV185-2500 mm²43-83 mm (to 1600 mm²); 60-112 mm (1600-2500 mm²)2000-3000 mm
EHVS-170TThree-piece, as above170 kV240-2500 mm²60-112 mm2000-3000 mm
Last letterOuter protection (S and T joints)
WHeat-shrink rejacketing with integrated moisture barrier
CCopper casing
BCoffin box
HHeavy duty: copper casing and coffin box

All EHVS joints use a torque-controlled connector and can be supplied for inline, shield-break or grounded screen treatment, so the joint matches its position in the bonding scheme. A fibre-optic add-on kit with gel sealing is available for straight-through and cross-bonding joints.

Connectors for the termination top

The top stud of an outdoor termination (30, 40, 50 or 60 mm, depending on type) is joined to the busbar or overhead line with a high-strength aluminium alloy connector, tightened with a socket wrench. Types in our records: NEMA terminal pad (holes 14.3 mm at 44.4 mm centres), straight rod, straight transition rod, T-rod, twin straight rod and twin T-rod.

Clamping rangeSuits top studExamples
26-31 mm30 mm707021-1 pad; 706684-1 rod; T 82 30 T-rod
36-41 mm40 mm707127-1 pad; 706685-1 rod; T 82 40 T-rod
46-51 mm50 mm718671-1 pad; 1510395-1 rod; T 82 50 30 T-rod
56-61 mm60 mm707216-1 rod; T 82 60 30 T-rod

Transition rods and T-rods have a second clamp, from 16-21 mm up to the size of the first, for the conductor on the other side, so give us both diameters.

Sheath bonding and link boxes

Current in a single-core HV cable induces voltage in its metallic sheath. Depending on how the sheaths are bonded, that voltage can drive circulating currents that heat the cable and reduce its rating. The usual schemes are single-point earthing on short sections, cross-bonding of equal sections so the induced voltages cancel, and cross-bonding with transposition where the cables are not laid symmetrically.

Raychem link boxes are stainless steel, type tested, with removable links and optional ZnO sheath voltage limiters (SVL); the maker gives short-circuit capability up to 40 kA for 1 second.

Link boxLayoutSheath voltage limitersBonding leadProtection
HVLB-E-S-0-1 / -x-11-phase earthing / 1-phaseNone / 1-6 kVSingle-core 70-300 mm²IP68, buried
HVLB-E-S-0-3 / -x-33-phase earthing / 3-phaseNone / 1-6 kVSingle-core 70-300 mm²IP68, buried
HVLB-E-S-0-66-linkNoneSingle-core 70-300 mm²IP68, buried
HVLB-C-S-x-6Cross-bonding1-6 kVSingle-core 70-300 mm²IP68, buried
HVLB-C-C-x-3Cross-bonding1-10 kVConcentric 70-300 mm²IP68, buried
HVLB-GND, EPPA-0551-phase or 3-phase, with or without SVLNone / 1-6 kVSingle-core 95-300 mm²IP56 (some IP68), not buried

Common questions

What is the difference between OHVT-C and OHVT-P?

Both are oil-filled outdoor terminations with a silicone-rubber stress cone. OHVT-C has a light, pressure-tight composite housing offered in more creepage lengths for polluted sites; OHVT-P has a porcelain housing.

Do PHVS and PHVT terminations need oil filling on site?

No. They are dry plug-in designs. The plug-in part goes into an epoxy insulator in the switchgear or transformer, which works in SF6 or an insulating liquid.

What do the letters W, C, B and H mean on EHVS joints?

They give the outer protection: W heat-shrink rejacketing with moisture barrier, C copper casing, B coffin box, and H heavy duty with copper casing and coffin box.

Which HV terminations need no oil or gel?

The heat-shrink IHVT, OHVT and LHVT terminations, the dry OHVT-D outdoor termination and the PHVS and PHVT plug-in terminations.

Can Six Winds select the HV accessories for our project?

We match Raychem part numbers to your cable drawing, voltage, equipment interface and site data. The final selection is confirmed by the project engineer against the maker's data and the specification.

Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.

This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.