Find Um and the BIL your specification asks for, then pick by where the cable ends: open air (OHVT heat-shrink, composite, porcelain or dry), indoors (IHVT), gas-insulated switchgear (PHVS) or a transformer (PHVT). Choose the outdoor creepage for the site pollution, the joint type and its outer protection, and plan the sheath bonding and link boxes with the cable route. Every HV kit is confirmed against the cable drawing before order.
Step by step
- Fix Um and the impulse levelTake the highest system voltage Um and the required lightning impulse (BIL) from the specification. The Raychem classes run 52, 72.5, 123, 145, 170 and 245 kV.
- Collect the cable dataConductor size and material, insulation diameter over the prepared insulation, maximum diameter over the outer sheath, metallic sheath or screen design, and any built-in optical fibres. The cable maker's drawing has all of these.
- Decide where each cable end goesOpen-air outdoor structure, indoor room, gas-insulated switchgear or transformer. This decides between OHVT, IHVT, PHVS and PHVT.
- Choose the outdoor creepageFor outdoor terminations, match the creepage distance to the site pollution level. Coastal, desert-dust and industrial sites often call for the longer variants.
- Choose the jointsHeat-shrink EHVS-H at 52-72.5 kV, one-piece EHVS-S or three-piece EHVS-T above that; then the outer protection (W, C, B or H) and the screen treatment (inline, shield break or grounded) that the bonding design needs.
- Plan connectors and sheath bondingPick the top connector for the busbar or line, then the link boxes for the bonding scheme: single-point earthing or cross-bonding, buried or above ground, with or without sheath voltage limiters.
- Send us the packageCable drawing, Um and BIL, number of terminations and joints of each type, switchgear or transformer interface, site pollution class and the bonding single-line diagram. We return the matching Raychem selection for your engineer to confirm.
Um, rated voltage and BIL
HV accessories are rated by Um, the highest voltage of the system they serve, with the cable's rated voltage U and the lightning impulse withstand (BIL) alongside. IEC 60840 covers the classes up to 170 kV in our records and IEC 62067 the 245 kV class; IEC 60815 is cited for outdoor creepage.
| Um | Rated voltage U | Lightning impulse (BIL) | Test standard | Terminations in our records | Joints |
|---|---|---|---|---|---|
| 52 kV | 45-47 kV | 250 kV | IEC 60840 | IHVT-52H, OHVT-52H | EHVS-52H |
| 72.5 kV | 60-69 kV | 325 kV | IEC 60840 | IHVT/OHVT/LHVT-72H, OHVT-72C, OHVT-72P, PHVS-72, PHVT-72 | EHVS-72H |
| 123 kV | 110-115 kV | 550 kV (OHVT-123P); 325 kV reduced level for OHVT-123H | IEC 60840 | OHVT-123H, OHVT-123P | - |
| 145 kV | 132-138 kV | 650 kV | IEC 60840 | OHVT-145C, OHVT-145P, OHVT-145D, PHVS-145, PHVT-145 | EHVS-145S, EHVS-145T |
| 170 kV | 150-161 kV | 750 kV | IEC 60840 | OHVT-170C, PHVS-170, PHVT-170 | EHVS-170T |
| 245 kV | 220-230 kV | 1050 kV | IEC 62067 | OHVT-245C, OHVT-245P, PHVS-245, PHVT-245 | EHVS-245S |
Terminations at a glance
| Family | Where it goes | How it is built | Um in our records | Conductor |
|---|---|---|---|---|
| IHVT-H | Indoor | Heat-shrink stress control tube with non-tracking outer tube and sheds; no oil or compound | 52, 72.5 kV | 95-2500 mm² |
| OHVT-H / LHVT-H | Outdoor; LHVT with extended creepage | As IHVT-H, longer and with greater creepage | 52, 72.5, 123 kV | 95-2500 mm² (123 kV: 95-1600; LHVT: 300-2500) |
| OHVT-C | Outdoor, including heavily polluted sites | Light, pressure-tight composite housing, factory-tested silicone-rubber stress cone, silicone-oil filled without preheating | 72.5, 145, 170, 245 kV | 95-2500 mm² (245 kV: 300-2500) |
| OHVT-P | Outdoor | Porcelain housing, silicone-rubber stress cone, silicone-oil filled | 72.5, 123, 145, 245 kV | 95-1200 mm² (245 kV: 300-2500) |
| OHVT-D | Outdoor, self-supporting | Dry: plug-in part with stress cone in an epoxy insulator with moulded silicone sheds; no oil or gel; short cable cut-back | 145 kV | 95-1200 mm² |
| PHVS | Gas-insulated switchgear (GIS) | Dry plug-in into an epoxy insulator; interface to IEC 62271-209; works in SF6 or insulating liquid | 72.5, 145, 170, 245 kV | 95-2500 mm² by class |
| PHVT | Transformers and other equipment | Dry, separable plug-in with corona shield; SF6 or insulating liquid such as transformer oil | 72.5, 145, 170, 245 kV | 95-2500 mm² by class |
Heat-shrink terminations are modular and need no filling. Composite and porcelain units carry a factory-tested silicone-rubber stress cone and are filled with silicone oil. The dry OHVT-D has no oil or gel, and its plug-in part can be fitted to the cable in the workshop beforehand.
Outdoor terminations: creepage and pollution
Creepage, the distance along the insulator surface, is what keeps an outdoor termination clean of flashover in dust, salt and industrial pollution. Composite OHVT-C housings come in several creepage lengths per class, up to 50 mm/kV, for common and extreme pollution levels.
| Um | OHVT-C composite (minimum creepage) | OHVT-P porcelain | Heat-shrink and dry-type |
|---|---|---|---|
| 52 kV | - | - | IHVT-52H approx. 1100 mm; OHVT-52H approx. 1540 mm |
| 72.5 kV | -2A 2164 mm; -2B 2383 mm; -2C 3089 mm | -72P-2A 2350 mm | IHVT-72H approx. 1600 mm; OHVT-72H approx. 2300 mm; LHVT-72H approx. 3100 mm |
| 123 kV | - | -123P-4B 3910 mm | OHVT-123H approx. 3100 mm |
| 145 kV | -2A 3392; -3A 3829; -4A 4684; -4B 6100; -4C 8047 mm | -145P-4A 4300 mm | OHVT-145D 4680 mm |
| 170 kV | -1A 3829; -3A 4273; -4A 5373; -4B 5746; -4C 9436 mm | - | - |
| 245 kV | -2A 5161; -3A 5605; -4A 6160; -4B 8401; -4C 10171 mm | -245P-4A 9100 mm | - |
Optional add-ons for outdoor terminations: arcing horns with an adjustable gap that keep flashovers off the insulator surface; a lifting device (terminations up to 170 kV, sheath up to 110 mm, up to 500 kg) so the termination can be built and filled on the ground and raised with its cable; an oil drain flange for drawing oil samples later; and a fibre-optic add-on kit for two steel pipes of up to 24 fibres each.
Plug-in terminations for switchgear and transformers
PHVS terminates the cable inside gas-insulated switchgear and PHVT inside transformers and similar equipment. Both are dry, with no oil filling on site: a plug-in part with a silicone-rubber stress cone goes into a pressure-tight epoxy insulator that the equipment maker can fit in advance. They work in SF6 or in an insulating liquid.
| Size | BIL | Conductor | Insulation diameter (prepared) | Max. sheath diameter | Min. creepage |
|---|---|---|---|---|---|
| PHVS-72 / PHVT-72 | 325 kV | 95-2000 mm² | 34-78 mm | 120 mm | 255 mm |
| PHVS-145 / PHVT-145 | 650 kV | 95-2500 mm² | 34-78 mm up to 1200 mm²; 73-108 mm from 1200 mm² | 120 / 135 mm | 414 mm |
| PHVS-170 / PHVT-170 | 750 kV | 1000-2500 mm² | 73-108 mm | 135 mm | 414 mm |
| PHVS-245 / PHVT-245 | 1050 kV | 300-2500 mm² | 77-119 mm | 150 mm | 519 mm |
Related parts: a re-usable blind plug closes the socket so the equipment can run at nominal voltage before the cable arrives, and a pressure-tested test plate lets the insulator be pressurised with SF6 during switchgear testing.
Joints: EHVS-H, EHVS-S and EHVS-T
| Joint | Design | Um | Conductor | Insulation diameter (prepared) | Length |
|---|---|---|---|---|---|
| EHVS-52H, -72H | Modular heat-shrink tubes over a torque-controlled connector; no special tools | 52, 72.5 kV | 95-2500 mm² | 30-86 mm | 1350 mm |
| EHVS-145S | One-piece pre-moulded silicone rubber body, factory tested | 145 kV | 500-2500 mm² | 60-112 mm | 2400-3000 mm |
| EHVS-245S | One-piece pre-moulded silicone rubber body, factory tested | 245 kV | 300-2500 mm² | 71-119 mm | 2500-3500 mm |
| EHVS-145T | Three-piece: main body plus two adapters; short cut-back, size transition possible | 145 kV | 185-2500 mm² | 43-83 mm (to 1600 mm²); 60-112 mm (1600-2500 mm²) | 2000-3000 mm |
| EHVS-170T | Three-piece, as above | 170 kV | 240-2500 mm² | 60-112 mm | 2000-3000 mm |
| Last letter | Outer protection (S and T joints) |
|---|---|
| W | Heat-shrink rejacketing with integrated moisture barrier |
| C | Copper casing |
| B | Coffin box |
| H | Heavy duty: copper casing and coffin box |
All EHVS joints use a torque-controlled connector and can be supplied for inline, shield-break or grounded screen treatment, so the joint matches its position in the bonding scheme. A fibre-optic add-on kit with gel sealing is available for straight-through and cross-bonding joints.
Connectors for the termination top
The top stud of an outdoor termination (30, 40, 50 or 60 mm, depending on type) is joined to the busbar or overhead line with a high-strength aluminium alloy connector, tightened with a socket wrench. Types in our records: NEMA terminal pad (holes 14.3 mm at 44.4 mm centres), straight rod, straight transition rod, T-rod, twin straight rod and twin T-rod.
| Clamping range | Suits top stud | Examples |
|---|---|---|
| 26-31 mm | 30 mm | 707021-1 pad; 706684-1 rod; T 82 30 T-rod |
| 36-41 mm | 40 mm | 707127-1 pad; 706685-1 rod; T 82 40 T-rod |
| 46-51 mm | 50 mm | 718671-1 pad; 1510395-1 rod; T 82 50 30 T-rod |
| 56-61 mm | 60 mm | 707216-1 rod; T 82 60 30 T-rod |
Transition rods and T-rods have a second clamp, from 16-21 mm up to the size of the first, for the conductor on the other side, so give us both diameters.
Sheath bonding and link boxes
Current in a single-core HV cable induces voltage in its metallic sheath. Depending on how the sheaths are bonded, that voltage can drive circulating currents that heat the cable and reduce its rating. The usual schemes are single-point earthing on short sections, cross-bonding of equal sections so the induced voltages cancel, and cross-bonding with transposition where the cables are not laid symmetrically.
Raychem link boxes are stainless steel, type tested, with removable links and optional ZnO sheath voltage limiters (SVL); the maker gives short-circuit capability up to 40 kA for 1 second.
| Link box | Layout | Sheath voltage limiters | Bonding lead | Protection |
|---|---|---|---|---|
| HVLB-E-S-0-1 / -x-1 | 1-phase earthing / 1-phase | None / 1-6 kV | Single-core 70-300 mm² | IP68, buried |
| HVLB-E-S-0-3 / -x-3 | 3-phase earthing / 3-phase | None / 1-6 kV | Single-core 70-300 mm² | IP68, buried |
| HVLB-E-S-0-6 | 6-link | None | Single-core 70-300 mm² | IP68, buried |
| HVLB-C-S-x-6 | Cross-bonding | 1-6 kV | Single-core 70-300 mm² | IP68, buried |
| HVLB-C-C-x-3 | Cross-bonding | 1-10 kV | Concentric 70-300 mm² | IP68, buried |
| HVLB-GND, EPPA-055 | 1-phase or 3-phase, with or without SVL | None / 1-6 kV | Single-core 95-300 mm² | IP56 (some IP68), not buried |
Common questions
What is the difference between OHVT-C and OHVT-P?
Both are oil-filled outdoor terminations with a silicone-rubber stress cone. OHVT-C has a light, pressure-tight composite housing offered in more creepage lengths for polluted sites; OHVT-P has a porcelain housing.
Do PHVS and PHVT terminations need oil filling on site?
No. They are dry plug-in designs. The plug-in part goes into an epoxy insulator in the switchgear or transformer, which works in SF6 or an insulating liquid.
What do the letters W, C, B and H mean on EHVS joints?
They give the outer protection: W heat-shrink rejacketing with moisture barrier, C copper casing, B coffin box, and H heavy duty with copper casing and coffin box.
Which HV terminations need no oil or gel?
The heat-shrink IHVT, OHVT and LHVT terminations, the dry OHVT-D outdoor termination and the PHVS and PHVT plug-in terminations.
Can Six Winds select the HV accessories for our project?
We match Raychem part numbers to your cable drawing, voltage, equipment interface and site data. The final selection is confirmed by the project engineer against the maker's data and the specification.
Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.
This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.