Match the VMVL size to the HID wattage (typical replacements: VMVL-3 for 70 W, VMVL-5 for 100 W, VMVL-7 for 175 W, VMVL-9 for 250 W, VMVL-11 for 320 W, VMVL-13 for 400 W). Keep the existing Champ mounting module and order the luminaire without one, or use a CHMM1 to CHMM4 adapter for Appleton, Thomas & Betts or GE mounts. Choose the UNV1 driver (100-277 VAC, 127-250 VDC) or UNV34 (347-480 VAC), and check the area classification still allows a Zone 2 / Division 2 fitting.
Step by step
- List the existing fittingsFor each point record the lamp type and wattage, the mounting style (pendant, cone pendant, ceiling, wall or stanchion), the hub size, the supply voltage and the hazardous area classification. A photo of the nameplate saves a site visit.
- Pick the VMVL sizeUse the typical replacement table below as a starting point, then confirm it with a lighting calculation for your mounting height and the light level your specification asks for.
- Decide on the mountingIf the existing Champ HID or LED mounting module stays, order the VMVL with no mounting module. If the old fitting is an Appleton MercMaster, Thomas & Betts HazLux or GE H2 Filtr-Gard, add the matching CHMM adapter. New points get a mounting code in the catalogue number.
- Choose the driver voltageUNV1 covers 100-277 VAC at 50/60 Hz and 127-250 VDC; UNV34 covers 347-480 VAC. The ATEX and IECEx markings in the brochure are for the UNV1 luminaire.
- Choose the optic and lensType V (standard) gives a round pattern, Type I a long narrow pattern for aisles and pipe racks, and Type III throws light to one side. Clear glass is standard; diffused glass, polycarbonate and an uplight refractor are options.
- Check the certification before you swapThe VMVL is a Zone 2 gas, Zone 21 dust and Class I Division 2 fitting. Confirm the zone, gas group and temperature class on the area drawing; a fitting in Zone 1 must not be replaced with a VMVL.
Typical VMVL size for each HID wattage
| Existing HID lamp (metal halide or HPS) | Typical Champ VMVL | Nominal lumens (UNV1) | LED watts (UNV1) | Watts saved against the lamp rating alone |
|---|---|---|---|---|
| 70 W | VMVL-3 | 3,302 lm | 27 W | about 61% |
| 100 W | VMVL-5 | 5,412 lm | 43 W | about 57% |
| 175 W | VMVL-7 | 7,327 lm | 57 W | about 67% |
| 250 W | VMVL-9 | 9,229 lm | 75 W | 70% |
| 320 W | VMVL-11 | 11,266 lm | 92 W | about 71% |
| 400 W | VMVL-13 | 13,582 lm | 92 W | 77% |
The maker's brochure does not print a full HID equivalence table, so the sizes above are typical replacements, not a promise of equal light on every job. Mounting height, optic and the required light level decide the final choice, so run a lighting calculation or send us the layout. The last column compares LED watts with the lamp rating only; the ballast of an HID fitting draws more on top of that, so the real saving is larger.
One pair is backed by the maker's own test: at a 15 ft (about 4.6 m) mounting height, a VMVL-7 was compared with a 175 W pulse-start metal halide fitting. With Type I optics the average illuminance was 0.62 fc against 0.45 fc, with Type III 0.61 against 0.53, and with Type V 0.69 against 0.51. The LED fitting gave the higher average while using less than half the lumens and the energy of the metal halide lamp.
Lumens, watts and efficacy: UNV1 and UNV34 drivers
| Model | UNV1 lumens | UNV1 watts | UNV1 lm/W | UNV34 lumens | UNV34 watts | UNV34 lm/W |
|---|---|---|---|---|---|---|
| VMVL-3 | 3,302 | 27 | 122 | 3,250 | 28 | 116 |
| VMVL-5 | 5,412 | 43 | 126 | 5,537 | 44 | 125 |
| VMVL-7 | 7,327 | 57 | 129 | 7,442 | 57 | 130 |
| VMVL-7 with S892 | 7,327 | 60 | 122 | 7,442 | 61 | 122 |
| VMVL-9 | 9,229 | 75 | 123 | 9,234 | 68 | 136 |
| VMVL-9 with S892 | 9,229 | 80 | 115 | 9,234 | 73 | 126 |
| VMVL-11 | 11,266 | 92 | 122 | 11,114 | 83 | 134 |
| VMVL-11 with S892 | 11,266 | 97 | 114 | 11,114 | 86 | 129 |
| VMVL-13 | 13,582 | 92 | 147 | 13,582 | 91 | 147 |
| VMVL-13 with S892 | 13,582 | 93 | 145 | 13,582 | 90 | 145 |
All models have a power factor of 0.90, total harmonic distortion below 15% and 6 kV surge protection. S892 is the redundant driver option (VMVL-7, 9, 11 and 13 only); it costs a few extra watts, as the table shows. On UNV1 the current ranges from 0.27-0.10 A for the VMVL-3 up to 1.10-0.34 A for the VMVL-13 across the voltage range, so existing lighting circuits normally carry far less load after the change.
The lumen figures are for the standard Type V optic. With Type I or Type III optics the measured output is a little lower (for example 6,844 lm Type I and 6,741 lm Type III for the VMVL-7, tolerance ±10%). Amber (5,200 lm) and green (4,300 lm) versions exist for wildlife-sensitive sites. Each luminaire weighs about 8.6 to 8.7 kg.
Keep the mounting: Champ modules and the four adapters
The VMVL housing is compatible with previous-generation Champ HID and LED mounting modules, so on a like-for-like Champ change the conduit, the module and its wiring stay where they are. Order the luminaire with no mounting module and fit it to the module in place. The maker's module series cover pendant (APM2, APM3, HPM2), cone pendant (BPM2, BPM3), ceiling (CM2, CM3), wall (TWM2, TWM3) and stanchion (JM5, PM5) mounts.
| Adapter | Fits the existing mount of |
|---|---|
| CHMM1 | Appleton MercMaster III |
| CHMM2 | Appleton MercMaster II |
| CHMM3 | Thomas & Betts HazLux |
| CHMM4 | GE H2 Filtr-Gard |
Where the old fitting is another make, one of these four adapters lets the VMVL sit on the existing mount. A separate driver compartment, lever-lock connectors and terminal blocks make the wiring quick to reach during the change and in later maintenance.
Worked example: 50 fittings on a 12-hour schedule
A tank farm has 50 pendant fittings with 400 W HID lamps that run 12 hours a day, every day. They are replaced with the Champ VMVL-13 on the UNV1 driver (92 W). To stay on the safe side the HID fitting is counted at 400 W; its ballast adds more, so the real saving is higher.
| 400 W HID (counted at 400 W) | Champ VMVL-13, UNV1 (92 W) | |
|---|---|---|
| Load of 50 fittings | 50 × 400 W = 20.0 kW | 50 × 92 W = 4.6 kW |
| Energy per day (12 h) | 20.0 kW × 12 h = 240 kWh | 4.6 kW × 12 h = 55.2 kWh |
| Energy per year (365 days) | 87,600 kWh | 20,148 kWh |
| Saving | 184.8 kWh per day · 67,452 kWh per year · 77% | |
Each fitting saves 308 W, which is 3.696 kWh a day and about 1,349 kWh a year. Fittings that stay on 24 hours a day, common in process units, double the yearly figure to 134,904 kWh. Multiply the kWh saved by your own tariff to put a value on it; the HID replacement calculator does this for your own quantities and hours.
Savings beyond the electricity bill
- Long life: the maker rates the VMVL for up to 60,000 hours at 55 °C ambient, so relamping trips into the classified area, each with its permit and access equipment, become rare.
- No breakable lamp: the solid-state light source has no filament or glass lamp, which suits areas with vibration and shock.
- No mercury: the luminaire contains no mercury or other hazardous substances, so there are no spent HID lamps to dispose of.
- Warranty: the maker gives a 5-year fixture warranty under its terms and conditions.
- Spare drivers: replacement driver kits exist for each size and voltage, including redundant-driver versions, so a fitting is repaired rather than replaced.
Check the area classification before you swap
An HID fitting being removed may carry a different rating from the new one. The Champ VMVL is certified for Class I Division 2, Zone 2 gas (Ex ec mb IIC) and Zone 21 dust (Ex tb IIIC). It is not a Zone 1 fitting. Compare the zone, gas group and temperature class on the hazardous area drawing with the VMVL marking for your model, driver and ambient temperature; the certification guide has the tables.
What to send us for a quotation
The existing lamp type and wattage, the quantity, the mounting style and hub size (or the make of the old fitting if it is not a Champ), the supply voltage, the area classification and the optic or lens you prefer. The Champ VMVL range page lists the models and spare drivers, and the catalogue number builder turns your choices into a part number. Or e-mail sales@sixwinds.com.sa.
Common questions
Does the Champ VMVL fit my existing Champ mounting?
Yes. The maker states the VMVL is compatible with previous-generation Champ HID and LED mounting modules. Order the luminaire with no mounting module and fit it to the module already installed.
Is the 77% energy saving guaranteed?
It is the maker's "up to" figure against HID fixtures. Your saving depends on which lamp is replaced and its ballast losses; replacing a 400 W lamp with the 92 W VMVL-13 gives 77% on lamp watts alone.
Which driver do I need for a 230 V lighting circuit?
UNV1. It covers 100-277 VAC at 50/60 Hz and 127-250 VDC. UNV34 is for 347-480 VAC supplies.
Can a VMVL replace an HID fitting installed in Zone 1?
No. The VMVL is certified for Zone 2 gas, Zone 21 dust and Class I Division 2. A Zone 1 point needs a fitting certified for Zone 1.
Can I replace only the driver later?
Yes. The driver sits in a separate compartment, and replacement driver kits are listed for each size and for both UNV1 and UNV34, including redundant-driver versions.
Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.
This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.