Marechal Ex plugs and sockets for hazardous areas: DXN, DX, SPeX and multicontact ranges, Ex markings and temperature classes

Marechal builds its plug and socket technology into Ex versions for areas where flammable gas, vapour or combustible dust can be present. The Zone 1/21 DXN and the metal DX ranges keep the built-in load-break switch, so a motor or pump in a hazardous area can be disconnected and padlocked on the spot.

By the Six Winds engineering team · Updated

Quick answer

Start from the area classification: zone, gas group and temperature class, dust group and maximum surface temperature, and the highest ambient. Choose a Zone 1/21 range (or a Zone 2/22 version only for Zones 2 and 22), check its T-class at your ambient, and fit it only with Ex cable glands and the matching Ex box, sleeve or handle.

Step by step

  1. Get the area classificationTake the zone (1, 2, 21 or 22), the gas group and temperature class, and the dust group from the site's hazardous-area drawing. Marechal Ex plugs and sockets are for Zones 1, 2, 21 and 22, not Zone 0 or 20.
  2. Choose the range by currentPNCX for 5 to 10 A, DXN1/DXN3/DXN6 for 20 to 63 A, DX1 to DX2 for 20 to 200 A in metal, SPeX up to 680 A single pole, and PXN12C, DXN25C or DXN37C for control and signal circuits.
  3. Check the temperature class at your ambientThe T-class printed on the device depends on the ambient. A DXN6 for Zone 1 is T5 up to +40 °C but T4 up to +60 °C.
  4. Check the certificatesAsk for the ATEX and IECEx certificate numbers, and any national scheme your project specifies, for every item.
  5. Use Ex glands and Ex accessoriesEach socket-outlet and inlet must sit on an Ex box, sleeve or handle, and every cable entry needs a certified Ex gland of the right size.
  6. Install and inspect to the Ex rulesInstallation follows IEC/EN 60079-14 and is done and inspected by competent persons. Never modify an Ex device.

Zones and equipment categories

Gas areas are divided into Zones 0, 1 and 2, and dust areas into Zones 20, 21 and 22, by how often an explosive atmosphere is present. Category 2 equipment (protection level Gb for gas, Db for dust) is made for Zone 1 and 21 and can also be used in Zone 2 and 22. Category 3 equipment (Gc, Dc) is for Zone 2 and 22 only.

Marechal offers the DXN ranges in both forms: a Zone 1/21 version, which keeps the load-break switch, and a Zone 2/22 version for areas where the hazard is rare or short-lived.

The Marechal Ex ranges

RangeCurrentHousing and sealingZonesEx marking
PNCX5 A (Zone 2/22 version 10 A)GRP, IP66/IP67/IP691, 2, 21, 22II 2 G D Ex e IIC T6 Gb / Ex tb IIIC T72 °C Db
DXN1, Zone 1/2120 AGRP, IP66/IP671, 2, 21, 22II 2 G D Ex db eb IIC T6 or T5 Gb / Ex tb IIIC T70 °C or T90 °C Db
DXN3, Zone 1/2132 AGRP, IP66/IP671, 2, 21, 22II 2 G D Ex db eb IIC T6 or T5 Gb / Ex tb IIIC T57 °C or T77 °C Db
DXN6, Zone 1/2163 AGRP, IP66/IP671, 2, 21, 22II 2 G D Ex db eb IIC T5 or T4 Gb / Ex tb IIIC T87 °C or T107 °C Db
DXN1/3/6, Zone 2/2220 / 40 / 63 AGRP, IP66/IP672, 22II 3 G D Ex ec IIC Gc / Ex tc IIIC Dc
DX1, DX3, DX6, DX9, DX220, 32, 63, 125, 200 AMetal, IP65/IP66, IK101, 2, 21, 22II 2 G D Ex de IIC tD A21
SPeX (single pole)up to 680 AGRP, IP65/IP661, 2, 21, 22II 2 G D Ex e IIC Gb / Ex tb IIIC Db

Load-break: the Zone 1/21 DXN1 is rated AC-22A and AC-23A (20 A at 440 V for motors), DXN3 and DXN6 are rated AC-22A, and the DX range also breaks load. The Zone 2/22 DXN versions are listed without breaking capacity. For control and instrument circuits, PXN12C (11+E), DXN25C (24+E) and DXN37C (36+E) carry signals from 4-20 mA up to 10 A in corrosion-protected metal housings, in Ex e or, on request, intrinsically safe (Ex ia/ib) versions.

How to read the Ex marking

Take the Zone 1/21 DXN1 as an example: II 2 G D Ex db eb IIC T6 or T5 Gb / Ex tb IIIC T70 °C or T90 °C Db.

  • II 2 G D: ATEX equipment group II, category 2, for gas (G) and dust (D).
  • Ex db eb: the switching chamber is a flameproof enclosure (db) that contains any internal ignition, while the housing and terminals are increased safety (eb), built so that sparks and hot spots do not occur.
  • IIC: the most demanding gas group (hydrogen, acetylene); it also covers IIA and IIB.
  • T6 or T5: maximum surface temperature of 85 °C or 100 °C, depending on ambient.
  • Gb / Db: equipment protection level for Zone 1 (gas) and Zone 21 (dust).
  • Ex tb IIIC T70 °C: dust protection by enclosure for Zone 21, suitable for conductive dust (IIIC), with a maximum surface temperature of 70 °C.

Zone 2/22 versions read Ex ec and Ex tc with Gc and Dc. The DX range carries the older form Ex de IIC tD A21: flameproof plus increased safety for gas, and dust protection for Zone 21.

Temperature class versus ambient

The surface temperature of a plug and socket rises with current and with ambient, so Marechal gives two classes for each device:

  • DXN1 and DXN3 (Zone 1/21): T6 up to +40 °C ambient, T5 up to +60 °C.
  • DXN6 (Zone 1/21): T5 up to +40 °C, T4 up to +60 °C.
  • DX1 and DX3: T6 up to +50 °C, T5 up to +60 °C (from -25 °C). DX6 and DX9: T6 up to +50 °C, T5 up to +60 °C (from -40 °C). DX2: T3 up to +60 °C.
  • SPeX: the class depends on current, cable size and ambient; on 240 mm² cable it carries 570 A at T5 with +40 °C ambient.

The device class must be at least as strict as the class the gas needs: T6 equipment also suits T5 to T1 areas. Take the highest ambient the device will really see, which outdoors in Saudi summer can exceed +40 °C.

ATEX and IECEx certification

The Ex ranges are certified under the European ATEX Directive 2014/34/EU and the international IECEx scheme, and built to IEC/EN 60079-0, -1, -7 and -31 together with IEC/EN 60309-1 and -4. Each range has its own certificate, for example IECEx LCI 09.0005X / LCIE 99 ATEX 6027 X for the Zone 1/21 DXN1. Several ranges also hold other national approvals and Bureau Veritas Marine approval. When a certificate number ends in X, read its specific conditions of use.

Ex cable glands and matching Ex boxes

An Ex plug or socket is only as safe as its cable entry. Each socket-outlet and inlet must be fitted to a box, sleeve or handle from the same Ex range, and each cable must enter through a certified Ex gland sized to its outer diameter.

  • DXN accessories: GRP wall boxes (30° or 70°) and handles come with an Ex polyamide gland, or a metal gland with earth continuity, chosen by cable diameter.
  • DX range: supplied with an Ex metal gland, M20 up to M63 depending on size.
  • Separate Ex glands: ATEX polyamide and ATEX metal glands from M16 to M63, plus ATEX-EMC metal glands for screened cables.
  • Ex boxes: B2X socket and junction boxes (II 2 G D Ex e IIC Gb / Ex tb IIIC Db, GRP, 120x120 or 160x160 mm, IP66/IP67) take DXN1, DXN3, DXN6, PNCX and PXN12C; MXBJ and MXBS boxes come in GRP, aluminium or 316L stainless steel.

Padlocking works in the hazardous area too: DXN sockets take the two-padlock locking pin, and DX sockets lock connected or disconnected with a lockable shaft.

What to send us for a quotation

The zone, gas group and temperature class, dust group, highest ambient, current, poles and voltage, mounting (wall box, sleeve or handle), cable outer diameter and conductor size, the certificates you need, and the quantity. The Marechal reference from an existing device is the quickest route. E-mail sales@sixwinds.com.sa or see the Marechal plugs and sockets page.

Common questions

Can I use a DXN Zone 2/22 version in Zone 1?

No. Zone 2/22 versions are category 3 (Gc, Dc) and are for Zones 2 and 22 only. Use the Zone 1/21 version in Zones 1 and 21; it can also be used in Zones 2 and 22.

Can I disconnect an Ex plug under load in a hazardous area?

With the Zone 1/21 DXN and the DX ranges, yes, within their switching rating, because the switch inside is flameproof. Zone 2/22 DXN versions are listed without breaking capacity and must be disconnected off-load.

Which temperature class do I need?

At least the class on the area drawing for the gas present. Then check the device's class at your highest ambient: many ranges drop one class above +40 °C or +50 °C.

Can I use an ordinary cable gland on an Ex socket?

No. Every cable entry needs a certified Ex gland of the right type and size, or the Ex protection of the whole assembly is lost.

Do you supply the ATEX and IECEx certificate details?

Yes. Ask for them with your enquiry and we include the certificate references for each item in our quotation.

Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.

This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.