العربية Get a quote

Technical guides

Elastimold separable connectors: 200 A loadbreak, 200 A and 600 A deadbreak, bushings, junctions, Ranger2 terminations and surge arresters

Separable connectors let a medium-voltage cable plug into a transformer, switchgear or junction through a fully shielded, insulated interface that can be taken apart again. The first choice is whether the connection must be operated with the circuit live (loadbreak) or only when it is dead (deadbreak); after that it is voltage class, current and the bushing on the equipment.

By the Six Winds engineering team · Updated

Quick answer

Use 200 A loadbreak elbows where crews must switch a circuit by hot stick under load in underground distribution circuits. Use 200 A or 600 A deadbreak (600 series, Cam-Op) for higher current and where connections are only made with the circuit de-energised and tested. Match the voltage class (15, 25 or 35 kV) and the equipment bushing, then size the elbow to the cable insulation diameter and conductor.

Step by step

  1. Fix the voltage classElastimold parts are grouped by class: 15 kV (95 kV BIL), 25 kV (125 kV BIL) and 35 kV (150 kV BIL), with some 200 A deadbreak and 600 A parts rated 15/25 kV. Use the class of the system, not just the cable.
  2. Fix the current200 A for taps and transformer loops; 600 A for main feeders and network cables, with 900 A versions that use copper current-carrying parts.
  3. Decide loadbreak or deadbreakLoadbreak if the connection will be opened or closed by hot stick with load on it; deadbreak if it will only be separated after the circuit is switched off, tested and grounded.
  4. Match the equipment interfaceA 200 A bushing well with a loadbreak insert, a 200 A deadbreak bushing, or a 600 A bushing. The elbow, insert and bushing must belong to the same system and class.
  5. Size to the cableIn catalogue numbers such as 165LR-W5X, W stands for the insulation-diameter code and X for the conductor-size code from the maker's tables; the middle digit picks the lug, for example 5 for bi-metal or 2 for all-copper on 200 A elbows. Give us insulation diameter, conductor size and material, and the shield type.
  6. Add the accessoriesTest point or direct test versions, insulated caps, parking bushings, grounding elbows or plugs, jacket seals and shield adapters, and shielded surge arresters at open points.
  7. Send us the listVoltage class, current, loadbreak or deadbreak, the equipment bushings, cable data and quantities. We match the Elastimold catalogue numbers and send them back for confirmation.

Loadbreak or deadbreak: the first decision

A loadbreak connector is built to make and break rated load current: a crew uses a hot stick to pull the elbow off its insert, and the separated elbow gives a visible disconnect point. A deadbreak connector has no such switching duty and is connected or separated only after the circuit is de-energised. Deadbreak systems carry higher currents and use bolted or pin-and-socket connections.

SystemOperationCurrentVoltage classes in our recordsTypical parts
200 A loadbreakCan make and break load current with a hot stick; visible disconnect point200 A continuous; 10 kA sym. for 10 cycles15, 25, 35 kVElbows 165LR/275LR/375LR, bushing inserts, feed-thrus, junctions, parking bushings
200 A deadbreakConnected and separated only when de-energised200 A15/25 kV156LR elbow with bail, straight receptacles and plugs, splices, junctions
600 series deadbreakDe-energised only; bolted T-body connections600 A continuous (900 A copper versions); 25 kA sym. for 10 cycles15/25, 35 kVK655LR and 755LR elbows, connecting plugs, insulating plugs, bushing extenders
Cam-OpDe-energised; cam lever opens, tests, grounds and isolates by hot stick with a visible break600 and 900 A; 25 kA sym. for 10 cycles15, 25, 35 kVCam-Op link, connector kits, mountable bushing, alignment bracket
600 Series separable jointsDe-energised; re-arranged with standard hand tools600 A; 25 kA sym. 10 cycles15/25 kV (5-28 kV), 140 kV BILStraight, wye and H joint packages with test points

Voltage classes, BIL and current

Voltage classPhase-to-groundPhase-to-phaseBIL200 A loadbreak elbow600 A elbow
15 kV8.3 kV14.4 kV95 kV165LR (166LR with test point)K655LR (15/25 kV)
25 kV15.2 kV26.3 kV125 kV275LR (276LR with test point)K655LR (15/25 kV)
35 kV21.1 kV36.6 kV150 kV375LR (376LR with test point)755LR

Current ratings in our records: 200 A loadbreak parts are rated 200 A continuous with 10 kA symmetrical for 10 cycles; 600 series parts 600 A continuous (900 A versions with copper parts) with 25 kA symmetrical for 10 cycles. All interfaces in the 200 A and 600 A systems follow IEEE 386, which is what lets elbows, inserts and bushings of the same class fit together.

The 200 A family: elbows, inserts and junctions

Loadbreak elbows come as standard (165LR, 275LR, 375LR), with a capacitive test point (166LR, 276LR, 376LR), with an integral jacket seal (LRJS), as repair elbows with an extended contact for remaking a joint after the cable has been cut back (ELR), as replacement elbows (RLR), as direct test elbows that allow voltage testing of the conductor through a meter adapter (DLR), as a fused elbow with a full-range current-limiting fuse (168FLRH) and as a bolted elbow with tap (167LRT).

On the equipment side, a loadbreak bushing insert (1601A4, 2701A4, 3701A4) fits into a 200 A bushing well and receives the elbow; the 200AT tool tightens it. Feed-thrus and 2-, 3- and 4-point junctions (with stainless steel bracket or U straps) add connection points for sectionalising and tapping cables. Insulated parking bushings hold a de-energised elbow on the parking stand, and insulated caps close unused bushings.

The 200 A deadbreak system (15/25 kV) uses the 156LR elbow held by a bail, deadbreak bushing inserts, straight receptacles and plugs, tee and in-line splices, locking and Y splices, and 2- to 4-point junctions. A locking splice can serve as a repair splice, allowing about 4 in of cable to be replaced.

The 600 A family: 600 series, Stick-Op, Cam-Op and ComboT

The 600 series is the deadbreak system for primary feeders and network cable. A T-body elbow (K655LR at 15/25 kV, 755LR at 35 kV) bolts onto a threaded stud in the equipment bushing and is closed with an insulating plug and cap; connecting plugs join two elbows back to back, and bushing extenders, reducing tap plugs and reducing tap wells adapt the interface. The 600ATM tool and a torque wrench are used for assembly.

  • Test and ground kits add a reducing tap plug so a de-energised 600 A connection can be tested and grounded from the front of the elbow.
  • Stick-Op kits use a loadbreak reducing tap plug and threaded lug so the connection can be operated by hot stick (600AT tool required).
  • Cam-Op uses pin-and-socket connectors and a cam-action lever: de-energised circuits can be opened, tested, grounded and isolated by hot stick with a visible break. The mountable bushing needs three threaded studs on the equipment faceplate.
  • ComboT is a 600 A or 900 A T-elbow supplied as one unit with bus and stud, with or without a test point.
  • 600 Series separable joints (straight, wye and H) connect 600 A cables in vaults and manholes through an insulated bus bar with test points: 15/25 kV class, 140 kV BIL.
  • J2 to J6 junctions are built to order: each position is a 200 A deepwell, a 600 A bushing or blank, at 4 in or 6½ in spacing, for 15, 25/28 or 35 kV.
  • PCJ joints are permanent pre-moulded straight joints with crimped connectors for direct burial, vaults and submersible service (15, 25 and 35 kV class; 110, 150 and 200 kV BIL).

Equipment bushings

Elastimold apparatus bushings are moulded epoxy with a stainless steel flange for welding or clamping into transformers, switchgear and other equipment insulated by air, oil or SF6. The bushing decides which connector system the equipment accepts.

Equipment bushingTakesExamples
200 A deepwell bushing well (short or long shank, with or without bail tabs)A 200 A loadbreak or feed-thru insert, which then takes a loadbreak elbowK1601PC-S1, K1601PC-T1 (15/25 kV)
200 A deadbreak bushing200 A deadbreak elbow, held by a bailK180S4, K180T4
600 A bushing (short, long or 12 in shank; aluminium or copper rod)600 series T-body elbow on a threaded studK650S1, K650T1, K675T1, 750S1, 750L12
600 A in-air bushingAs above, for bushings used in air (boot and collars 600BC)K650TBC, K675TBC

Ranger2 terminations and shielded surge arresters

Ranger2 is a shrink-fit silicone termination for XLPE and EPR cable from #2 AWG to 1250 kcmil. The housing comes pre-expanded on a removable core with an integral stress-control tube, so no heat is needed; kits include silicone grease and self-fusing tape and have a pull-down jacket seal. The last letters give the cable shield (J concentric neutral, M tape or wire shield, L LC or wire-over-tape shield) and the insulation range (1: 16.3-28.4 mm, 2: 21.3-35.1 mm, 4: 33.0-53.3 mm). Ambient range -30 °C to 65 °C; optional JB clamp brackets support the cable.

Ranger2UseBILShedsCreepageMax. design voltage to ground
R2IT15…Indoor, 15 kV (IEEE 48 Class 2)110 kV0213 mm9.5 kV
R2T15…Outdoor, 15 kV (IEEE 48 Class 1A)110 kV4381 mm9.5 kV
R2T28…Outdoor, 25/28 kV150 kV6579 mm16 kV
R2T35…Outdoor, 35 kV200 kV8762 mm22 kV

Shielded MOV surge arresters protect the open end of a cable loop: BSA mounts on a 200 A bushing interface and carries its own fully rated 200 A loadbreak bushing, ESA is an elbow-form arrester for a 200 A loadbreak bushing (156ESA for 15/25 kV deadbreak), and PSA sits on the equipment parking stand, leaving the bushing free. Each comes with a 36 in #4 AWG ground lead. The rating is chosen by duty-cycle voltage and MCOV:

Duty-cycle ratingMCOV15 kV class25 kV class
3 kV2.55 kV167BSA-3, 167ESA-3, 167PSA-3-
6 kV5.10 kV167BSA-6, 167ESA-6, 167PSA-6-
10 kV8.40 kV167BSA-10, …273BSA-10, 273ESA-10, 273PSA-10
12 kV10.20 kV167BSA-12, …273BSA-12, …
15 kV12.70 kV167BSA-15, …273BSA-15, …
18 kV15.30 kV167BSA-18, …273BSA-18, …
21 kV17.00 kV-273BSA-21, 273ESA-21, 273PSA-21

Safety notes: switching, test and ground

  • Only loadbreak parts may be operated under load, and only by hot stick, with the elbow, insert and bushing all of the same loadbreak system and class.
  • Deadbreak connections (200 A deadbreak, 600 series, Cam-Op) are separated de-energised. Switch off, test for voltage and ground before removing a deadbreak elbow or plug.
  • Test before you ground. Test points, direct test elbows and test-and-ground kits exist so the circuit can be checked with a rated voltage tester before grounding elbows (1/0 AWG x 6 ft lead) or grounding plugs (2/0 AWG x 30 in lead on 600 series) are applied.
  • Park, do not drop. A removed elbow goes onto an insulated parking bushing, and an unused bushing is closed with an insulated cap.
  • Ground every shield. Connect the cable shield and the ground leads of elbows and arresters as the instructions require; jacket seals with ground leads (-SG kits) help where the shield must be bonded at the connector.
  • Follow the utility's switching procedure and the maker's instructions. This guide does not replace either, nor training for live-line work.

Common questions

Can a 600 A deadbreak elbow be removed under load?

No. 600 series and Cam-Op connectors are deadbreak: they are separated only after the circuit is de-energised, tested and grounded. For hot-stick operation under load use a 200 A loadbreak interface.

What is the difference between a bushing well and a bushing insert?

The bushing well is fixed in the transformer or switchgear. The loadbreak (or feed-thru) insert screws into the well and is the part the loadbreak elbow plugs onto, so a damaged insert can be replaced without changing the well.

What does a test point on an elbow do?

It gives a capacitive point on the elbow where a suitable indicator can show whether the cable is energised without removing the elbow. Direct test elbows go further and allow direct voltage testing of the conductor with a meter adapter.

How do I choose the surge arrester rating?

Choose the duty-cycle rating whose MCOV is at least the highest continuous phase-to-ground voltage of your system, within the 15 kV or 25 kV class of the equipment. Your protection engineer confirms the final rating.

Does a Ranger2 termination need a torch?

No. It is a cold shrink (shrink-fit) design: the silicone housing is held open on a removable core and shrinks onto the cable when the core is pulled out.

Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.

This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.