A NEMA code such as L14-30P tells you everything: L means locking, 14 is the voltage and wiring family (125/250 V, 4 wires), 30 is the current in amps and P means plug (R receptacle, C cord connector). Match the code exactly, check that the circuit voltage suits the family (5-series is 125 V only), and pick hospital grade, tamper-resistant or GFCI where the place needs it.
Step by step
- Read the code on the equipment plugNote the NEMA configuration (for example 5-20P or L6-30P) from the plug face or the nameplate.
- Check the voltage on site5-series devices are 125 V only; 6-series are 250 V; 14-series are 125/250 V with a neutral.
- Choose straight blade or lockingUse locking (L) devices where vibration or cable pull could disconnect the load.
- Choose the grade for the placeHospital grade in patient care areas, tamper-resistant where children are, GFCI near water, Ex in classified areas.
- Order plug, receptacle and connector by codeP for the plug, R for the fixed receptacle, C for the cord connector, with plates, boxes and cable size.
Why US plugs matter in Saudi projects
Saudi Arabia runs at 60 Hz, like North America, so a great deal of US-built equipment is installed here: medical devices, laboratory analysers, UPS and data-centre racks, compressors, welders and packaged plant. Many hospitals and industrial plants were also designed to US codes (the NEC and NFPA 99). That equipment arrives with NEMA plugs, and the site needs matching NEMA receptacles, connectors and spare plugs, not adaptors.
How to read a NEMA code
Every NEMA wiring device has a code in the form [L]family-amps[P/R/C]:
| Part | Meaning | Example: L14-30P |
|---|---|---|
| L (optional) | Locking (twist-lock) device; no L means straight blade | Locking |
| Family number | Voltage, phases and number of wires | 14 = 125/250 V, 3 poles, 4 wires |
| Amps | Current rating | 30 A |
| P / R / C | Plug, receptacle (fixed outlet) or cord connector | P = plug |
A plug only fits a receptacle with the same family and rating. The exceptions are deliberate: a 5-20R (T-slot) receptacle also takes a 5-15P plug, and a 6-20R takes a 6-15P.
Straight-blade configurations
| Code | Rating | Wiring | Typical use |
|---|---|---|---|
| 1-15 | 125 V, 15 A | 2-pole, 2-wire (no ground) | Old or double-insulated small appliances |
| 5-15 | 125 V, 15 A | 2-pole, 3-wire | Most US equipment cords, offices, medical carts |
| 5-20 | 125 V, 20 A | 2-pole, 3-wire | Hospital and commercial outlets, larger loads |
| 6-15 / 6-20 / 6-30 / 6-50 | 250 V | 2-pole, 3-wire (no neutral) | 208–240 V equipment, compressors, welders, servers |
| 7-15 / 7-20 / 7-30 / 7-50 | 277 V | 2-pole, 3-wire | 277 V lighting and equipment circuits |
| 14-30 / 14-50 | 125/250 V | 3-pole, 4-wire | Dryers, ranges, generators, site power |
| 15-15 to 15-60 | 250 V three-phase | 3-pole, 4-wire | Three-phase equipment |
Older families without a grounding pole still appear on existing equipment: 2 (250 V, 2-wire), 10 (125/250 V, 3-wire), 11 (250 V three-phase, 3-wire) and 18 (120/208 V three-phase wye, 4-wire). Match them for replacements, but use grounding types (6, 14, 15 or L21) for new work.
Recognise the receptacle by its slots
The slot shapes tell you the configuration even when the face carries no marking:
- 5-15R: two vertical slots (the taller one is the neutral) and a round ground hole.
- 5-20R: the neutral slot has a sideways T, so it takes both 5-15P and 5-20P plugs.
- 6-15R: two horizontal slots and a ground hole: 250 V, no neutral.
- 6-20R: one slot has a T, so it takes 6-15P and 6-20P plugs.
| Receptacle | Rating | Maximum load | Continuous load (80%) |
|---|---|---|---|
| 5-15R | 15 A, 125 V | 1,800 W at 120 V · 1,900 W at 127 V | 1,440 W at 120 V |
| 5-20R | 20 A, 125 V | 2,400 W at 120 V · 2,540 W at 127 V | 1,920 W at 120 V |
| 6-15R | 15 A, 250 V | 3,450 W at 230 V · 3,600 W at 240 V | 2,760 W at 230 V |
| 6-20R | 20 A, 250 V | 4,600 W at 230 V · 4,800 W at 240 V | 3,680 W at 230 V |
Watts = volts × amps. US practice (NEC) limits a load that runs for three hours or more to 80% of the circuit rating. The Saudi figures use 230 V for the 6-series and 120–127 V for the 5-series.
Download the printable NEMA plug chart (A4 PDF)
Locking (twist-lock) configurations
Locking devices turn and lock in place, so a plug cannot be pulled out by a tug on the cable or by vibration. They are the usual choice for machines, generators, stage and site power and data-centre racks.
| Code | Rating | Wiring | Typical use |
|---|---|---|---|
| L1-15 / L2-20 | 125 V / 250 V | 2-pole, 2-wire (no ground) | Older equipment; replacements only |
| L5-15 / L5-20 / L5-30 | 125 V | 2-pole, 3-wire | Machines, tools, site distribution |
| L6-15 / L6-20 / L6-30 | 250 V | 2-pole, 3-wire | Rack PDUs, UPS, 208–240 V equipment |
| L7-15 / L7-20 / L7-30 | 277 V | 2-pole, 3-wire | Lighting circuits |
| L8-20 / L8-30 | 480 V | 2-pole, 3-wire | 480 V single-phase loads |
| L9-20 / L9-30 | 600 V | 2-pole, 3-wire | 600 V single-phase loads |
| L14-20 / L14-30 | 125/250 V | 3-pole, 4-wire | Portable generators, transfer inlets |
| L15-20 / L15-30 | 250 V three-phase | 3-pole, 4-wire | Three-phase machines |
| L16-20 / L16-30 | 480 V three-phase | 3-pole, 4-wire | Industrial machines |
| L21-20 / L21-30 | 120/208 V three-phase wye | 4-pole, 5-wire | Three-phase PDUs, stage power |
| L22-20 / L22-30 | 277/480 V three-phase wye | 4-pole, 5-wire | Industrial distribution |
Above 30 A, or where water and wash-down are present, UL 1682 pin and sleeve devices (20, 30, 60 and 100 A, up to IP67 / IP69K) are the better choice. We list a full range of them.
Hospital-grade devices
Hospital-grade receptacles and plugs are tested to extra requirements in UL 498: stronger grounding contacts, higher plug retention, and better resistance to impact and abuse. They carry a green dot on the face. In US-based hospital designs they are used in patient care spaces, where a loose ground or a plug that falls out is a real risk.
- Hospital-grade plugs belong on medical equipment cords too, not only on the wall.
- Tamper-resistant (TR) receptacles with internal shutters are used in paediatric and psychiatric areas and waiting rooms.
- Emergency (essential) branch receptacles are identified by a distinctive colour or marking; red devices or plates are common.
- Isolated-ground receptacles (orange, or marked with an orange triangle) are used where the design asks for them for sensitive equipment.
- GFCI protection (Class A, trips at about 5 mA) is used near sinks and in wet locations.
Hospital codes such as NFPA 99 also ask for periodic testing of receptacles in patient care rooms (polarity, grounding and blade retention). Worn receptacles that no longer grip the plug should be replaced with hospital-grade ones.
Industrial and hazardous areas
- Industrial grade devices have tougher housings, better cord grips and higher impact resistance than commercial ones; choose them in workshops and plants.
- Locking devices stop machines and generators being disconnected by accident.
- Wash-down and food areas: use watertight UL pin and sleeve devices or sealed NEMA devices with boots.
- Hazardous areas: use explosion-proof receptacles and plugs (factory-sealed or interlocked) certified for the Class and Division or Zone; ordinary NEMA devices are never acceptable there.
- Data centres: rack PDUs commonly use L6-30, L21-30 or IEC C13/C19 cords; match the PDU input plug to the receptacle on the floor.
The supply voltage in Saudi Arabia
The frequency is 60 Hz, like the US. The voltage is not always the same: new installations are 230/400 V, while some older buildings still have 127/220 V supplies.
- 5-series (125 V) receptacles must only be fed at 120–127 V. For 120 V equipment on a 230 V system, use a step-down transformer and a 5-series outlet on its secondary. Never connect a 5-15R or 5-20R to 230 V: the US equipment plugged into it would be damaged and could be dangerous.
- 6-series (250 V) devices suit 208–240 V equipment. They have no neutral pole; confirm with the equipment maker and the project engineer before using them on a 230 V line-to-neutral circuit.
- Label outlets with their voltage where 120 V and 230 V outlets are installed in the same room.
What to send for a quotation
- The NEMA code of each device (or a photo of the plug face or the equipment nameplate).
- Plug, receptacle, cord connector or inlet, and the quantity of each.
- The grade: hospital, tamper-resistant, GFCI, industrial, weather-resistant or explosion-proof.
- Colour, wall plates or boxes, and the cable size for plugs and connectors.
- The supply voltage at the outlet.
Our NEMA plug finder gives the code for any voltage and current, and the US NEMA plugs and receptacles page lists the devices we supply.
Common questions
What is the difference between 5-15 and 5-20?
Both are 125 V. A 5-15 is rated 15 A; a 5-20 is rated 20 A and its receptacle has a T-shaped neutral slot, so it accepts both 5-15P and 5-20P plugs. A 5-20P plug, with one horizontal blade, does not fit a 5-15R.
What does the green dot on a receptacle mean?
It marks a hospital-grade device, tested to the additional hospital-grade requirements of UL 498 for grounding, retention and strength.
Can I use an adaptor instead of the right NEMA receptacle?
Not in hospitals or plants. Adaptors loosen, can lose the ground and do not change the voltage. Fit the correct receptacle, or a transformer where the voltage differs.
Which twist-lock plug is used on portable generators?
Usually L14-30 (125/250 V, 30 A, 4-wire) and L5-30 on smaller sets; check the generator's outlet panel.
Are NEMA devices suitable for Saudi 60 Hz supplies?
Yes, the frequency matches. What must be checked is the voltage: 5-series devices are for 120–127 V circuits only.
Do you supply UL pin and sleeve devices?
Yes: plugs, connectors, receptacles and inlets from 20 to 60 A in 2-pole to 4-pole versions, IP44 to IP67 / IP69K.
Need these items? E-mail your list or a nameplate photo to sales@sixwinds.com.sa, or use the RFQ form.
This guide is general information. Final selection must follow the project design, the applicable standards and the maker's data.
